background image

 

LT0186 Issue 2.80 

         27 July 2012 

Page 6 of 10 

 

   

FLT 0V

 

VBF+

 

 

 

 

 

    

ALM-

 

0V

   

0V

   

FLT

 

+24V

   

NC

 

SUP

 

NO

 

C

 

 

MX1

ANCIL

Relay

(See 

Note 1)

 

 

10K

 

T-GEN 50

3U Panel
(FP0698)

  

   

 

 

 

  

 

+24V

0V

 

NO Fault

 

COM

 

 

 

ALM-

 

 

 

FLT

 

 

FLT 0V

   

ALM- 

   

+24V

   

0V

   

RED

 

YELLOW

 

YELLOW

 

BLACK

 

BLUE

 

Note 2

  

   

ALM-

 

FB

 

 

 

 

 

    

FLT 0V

 

+24V

 

   

 

FLT

 

COM

 

0V

 

 

NO

 

 

4100ES

(Note 7)

4100-3003

Relay Module

 

10K EOL

 

SPS Aux

Power

+24V
0V

Relay &

FB Input

3.4 T-GEN Wiring - Separate Alarm & Fault Wiring 

 

 

 
 
 
 
 
 
 
 
 
 
 

 

 

 
 
 
 
 
 
 
 
 
 
 
Notes 

1.   Please refer to MX1 LT0360 Installation Manual (NZ) or LT0439 Operator Manual (Australia) for more information.  

Use LM0319 (MX1/T-GEN Loom) or FP0698 3U Panel (see Note 2). 

2.  FP0698 3U panel comes with premade loom with connector for MX1 use (ANC1 J4).  For use with other panels 

remove connector and wire as shown above. 

3.  Requires connection to a monitored 24V supply (FP1600/Sigma 5/Omega 64 Mk3/4100ES). 
4.   Switch SW4 ON for the Master T-GEN. Fit LK7 in Relay Position for all T-GENs. 
5.   FP1600/Omega 64 Mk3 boards have three 7-segment displays.  
6.   ELD value depends upon Input type (not fitted when used with MX1 or 4100ES). 
7.  The SPS Aux Power output is rated at 2A which is sufficient to power only 1 T-GEN 50 with a maximum speaker load 

of 40W. Please refer to LT0394 or LT0350 for further details on using the T-GEN 50 with the 4100ES panel. 

 

 

 

 
 

Input IOR

 

ADR

 

ADM

 

13

 

X

 

etc

 

FLT

 

FLT 0

 

V

 

T

 

-

 

GEN 50

 

Master

 

(

 

Note 4) 

 

+

 

24

 

V

 

+

 

24

 

V

 

0

 

V

 

0

 

V

 

SIG

 

NO

 

COM

 

Fault

 

ALM -

 

 

 

+

 

24

 

V

 

0

 

V

 

ALM -

 

 

 

FLT

 

T-

 

GEN 50

 

Slave

 

(

 

Note  4)

 

+

 

24

 

V

 

+

 

24

 

V

 

0

 

V

 

0

 

V

 

SIG

 

NO

 

COM

 

Fault

 

ALM -

 

 

 

ELD

 

(

 

see Note 6 

 

)

 

FLT0

 

V

 

Open 

Collector 

Output

 

IOR

 

F

 

3200 etc

 

ELD 

10

 

K

 

0

 

V

 

ALM -

 

 

 

FP

 

1600 MK

 

3

 

Sigma 5

 

Omega 64 

MK

 

3

 

(

 

See

 

 Note 5

 

)

 

E

 

.g

 

.

 

, PA

 

0729 GP Relay Board (12V Relay)

 

ALM -

 

0

 

V

 

FLT

 

10K

 

FLT0

 

V

 

BELLS 

C

 

/+

 

BELLS -

 

See Note 3

 

ELD 

10

 

K

 

ALM -

 

 

0

 

V

 

Relay Output

 

F

 

3200 Relay Bd

 

,

IOR

 

, ADC

 

130

 

WARNING 

 

If powering a  

T-GEN50 via the 

SPS Aux power 

output the 

speaker load 

must not exceed 

40W 

Содержание T-GEN 50

Страница 1: ...S These instructions apply to units with V1 70 software onwards Refer to LT0186 Issue 2 30 for instructions for earlier software versions A pre assembled Building Occupant Warning System BOWS that uti...

Страница 2: ...lic address This is activated when the microphone s PTT button is pressed while the A I E switch is in the Auto or Evac position Public address overrides Alert and Evac tones A remote microphone can b...

Страница 3: ...e Recorded Message OFF ON OFF Present ISO8201 keywords Msg 1 Msg1 Evacuate the building using the nearest fire exit OFF ON ON Don t Care TEST mode Msg2 Evacuate as directed x2 ON OFF OFF None Wail sou...

Страница 4: ...the end of the line If wiring on two branches then two 100k ELDs are used one on each branch The capacitors must be bipolar and their value should be 1 5uF per Watt of their speaker s load see below S...

Страница 5: ...esistor from the Isolate switch and blank off the word Isolate on the label ISOL 24V AUTO Yellow LED 2K7 0V EVAC ISOL AUTO ELD 0V EVAC COM A I E Switch Wiring Figure A Isolate Indication via Spare Swi...

Страница 6: ...mega 64 Mk3 4100ES 4 Switch SW4 ON for the Master T GEN Fit LK7 in Relay Position for all T GENs 5 FP1600 Omega 64 Mk3 boards have three 7 segment displays 6 ELD value depends upon Input type not fitt...

Страница 7: ...to enable Fault Relay Turn SW4 off 3 RRM must be inside FIP and wired to RESP IN 4 Connect wire from NC terminal of relay to S pin of supervision link Do not fit Sup link at all 5 3k3 ELD for MX4428 A...

Страница 8: ...L see Note 1 Sigma 5 FP1600 Mk3 Note 3 OMEGA 64 Mk3 Note 3 0V 3 7 Earth Connection The T GEN must be connected to the cabinet EARTH using either the EARTH terminal on the T GEN PCB located beside the...

Страница 9: ...upplied fitted to provide a complete functional unit A loom for power control and monitoring is factory fitted The loom is connectorised for direct use with MX1 The connector can be removed and the lo...

Страница 10: ...T0186 Issue 2 80 27 July 2012 Page 10 of 10 Manufactured Tyco Fire Protection Products Distributed by 17 Mary Muller Drive PO Box 19 545 by Christchurch New Zealand Tel 64 3 389 5096 Fax 64 3 389 5938...

Отзывы: