background image

 

LT0186 Issue 2.80 

         27 July 2012 

Page 3 of 10 

CONFIGURATION 

 
1. 

Dip Switch settings

 

 

Sw1 (T0) 

Sw2 (T1) 

Sw3 (T2) 

Alert to Evacuate 

Change-Over Time 

  Sw4 (Mon) 

Alarm I/P  Fault Supervision 

OFF 

OFF 

OFF 

0 sec 

 

OFF 

 Disabled 

ON 

OFF 

OFF 

30 sec 

 

ON 

 Enabled 

OFF 

ON 

OFF 

1 min 

 

 

 

ON 

ON 

OFF 

1.5 min 

 

Sw5 (Lat) 

Alarm I/P (PA0766) 

OFF 

OFF 

ON 

3 min 

 

OFF 

Non-Latching 

ON 

OFF 

ON 

5 min 

 

ON 

Latching 

OFF 

ON 

ON 

10 min 

 

 

 

ON 

ON 

ON 

Alert Only 

 

Sw5 (Lat) 

Alert Tone (/PA0886) 

 

 

 

 

 

OFF 

No Alert Tone 

 only recorded message 

Sw6 (Ev0)

 

Sw7 (Ev1) 

Evacuate Tone

 

 

ON 

Alert tone plus recorded message 

 

 

PA0766

 

 

OFF 

OFF 

AS2220 

 

Sw8 (Att) 

Evacuate Message Selection (PA0766) 

ON 

OFF 

RH3 

 

 

(relative to Evac Tone) 

OFF 

ON 

I keywords 

 

OFF 

Msg1 or field recorded 

ON 

ON 

Wail (LK4 not fitted)

 

 

ON 

Msg2 in AS2220 or Keywords only in ISO8201 

ON 

ON 

Hee Haw (LK4 fitted) 

 

 

 

 
 

SW6 

(Ev0) 

SW8 

(Att) 

LK4 

(test) 

Evac 

Message 

Evac Tone (PA0886) 

 

Sw7 

(Ev1) 

Message Control (PA0886) 

OFF 

OFF 

Don’t 

Care 

None 

AS2220 evacuate only 

 

OFF 

Recorded Message stops on Input 
Cancel 

OFF 

OFF 

OFF 

Present 

AS2220 plus Msg1 

 

ON 

Recorded Message Plays at least 
once 

OFF 

OFF 

ON 

Present 

AS2220 plus Msg2 

 

 

 

OFF 

ON 

OFF 

None 

I keywords 

 

Name 

Recorded Message 

OFF 

ON 

OFF 

Present 

I ke 
Msg 1  

 

Msg1 

“Evacuate the building using the 
nearest fire exit”

 

OFF 

ON 

ON 

Don’t Care

 

TEST mode 

 

Msg2 

“Evacuate as directed” x2

 

ON 

OFF 

OFF 

None 

Wail sound, no message 

 

Alert 

“The fire ala

rm system has 

operated. Standby for further 

instructions”

 

ON 

OFF 

OFF 

Present 

Msg1 only 

 

ISO8201 

Keywords 

“Emergency”    “Evacuate Now”

 

ON 

OFF 

ON 

Don’t Care

 

TEST mode 

 

 

 

ON 

ON 

OFF 

Don’t Care

 

RH3 sound, no message 

 

 

 

ON 

ON 

ON 

Don’t Care

 

TEST mode 

 

 

 

 

 

2. Links 

 

Link 

Name 

Function  

BIAS 

Amplifier bias disable. Fit link to reduce quiescent current if T-GEN is to be used with tones only 
(no speech or background music).  

MASTER 

Fit for master, remove for slave. 

REC EN 

Fit to record message.  Refer OPERATION. 

TEST 

Fit for test tone (500Hz pulsing on/off at -

30dB). Operates in “Auto” only  and excludes AS2220 

for PA0886, Wail & Hee Haw.  

SLAVE 

Fit for slave mode only. Read only on power up. 

SLAVE / MASTER 

Selects slave or master mode - fit as appropriate. 

FAULT= 

DEF-/RELAY 

Enables the operation of either the Fault Relay or the DEF- output. 
Fit in DEF- or RELAY position as appropriate. (DEF- used on NZ panels only) 

 
 

3. Level 

Controls 

 

Control 

Name 

Function  

VR1 

BIAS 

Amplifier Bias 

 Factory adjustment only. 

VR2 

SPEECH VOL 

Volume adjustment for recorded messages. 

VR3 

PA VOL 

Volume adjustment for PA microphone. 

 
 

Содержание T-GEN 50

Страница 1: ...S These instructions apply to units with V1 70 software onwards Refer to LT0186 Issue 2 30 for instructions for earlier software versions A pre assembled Building Occupant Warning System BOWS that uti...

Страница 2: ...lic address This is activated when the microphone s PTT button is pressed while the A I E switch is in the Auto or Evac position Public address overrides Alert and Evac tones A remote microphone can b...

Страница 3: ...e Recorded Message OFF ON OFF Present ISO8201 keywords Msg 1 Msg1 Evacuate the building using the nearest fire exit OFF ON ON Don t Care TEST mode Msg2 Evacuate as directed x2 ON OFF OFF None Wail sou...

Страница 4: ...the end of the line If wiring on two branches then two 100k ELDs are used one on each branch The capacitors must be bipolar and their value should be 1 5uF per Watt of their speaker s load see below S...

Страница 5: ...esistor from the Isolate switch and blank off the word Isolate on the label ISOL 24V AUTO Yellow LED 2K7 0V EVAC ISOL AUTO ELD 0V EVAC COM A I E Switch Wiring Figure A Isolate Indication via Spare Swi...

Страница 6: ...mega 64 Mk3 4100ES 4 Switch SW4 ON for the Master T GEN Fit LK7 in Relay Position for all T GENs 5 FP1600 Omega 64 Mk3 boards have three 7 segment displays 6 ELD value depends upon Input type not fitt...

Страница 7: ...to enable Fault Relay Turn SW4 off 3 RRM must be inside FIP and wired to RESP IN 4 Connect wire from NC terminal of relay to S pin of supervision link Do not fit Sup link at all 5 3k3 ELD for MX4428 A...

Страница 8: ...L see Note 1 Sigma 5 FP1600 Mk3 Note 3 OMEGA 64 Mk3 Note 3 0V 3 7 Earth Connection The T GEN must be connected to the cabinet EARTH using either the EARTH terminal on the T GEN PCB located beside the...

Страница 9: ...upplied fitted to provide a complete functional unit A loom for power control and monitoring is factory fitted The loom is connectorised for direct use with MX1 The connector can be removed and the lo...

Страница 10: ...T0186 Issue 2 80 27 July 2012 Page 10 of 10 Manufactured Tyco Fire Protection Products Distributed by 17 Mary Muller Drive PO Box 19 545 by Christchurch New Zealand Tel 64 3 389 5096 Fax 64 3 389 5938...

Отзывы: