INPUT WIRING DETAILS

 

 

3.1  Auto/Isolate/Evac Switch. 

 

     

 

 

 

 
The use of the Auto/Isolate/Evac switch is not recommended in fire panels compliant with AS 4428.1 or AS 7240.2, as 
the isolate facility on this switch is a duplication of the AS 4428 Warning System Isolate or AS 7240 Alarm Devices 
Disable function already provided on these panels, and there is no indication of the Isolate position.   
 
However, the switch may be useful with older AS1603.4 fire panels, in which case the Isolate position should be 
indicated. 
 
An LED (and resistor) could be wired to turn on in the Isolate position via a spare switch contact (Figure B), or a fault 
could be generated on the fire panel when the switch is in the Isolate position.  For example, wire the ELD 0V connection 
through the Auto and Evacuate switch contacts so a fault is generated in the Isolate position (Figure C). 
 
Alternatively, if the Isolate position is to be disabled (but the Auto and Evacuate positions retained) remove the 10k 
resistor from the Isolate switch and blank off the word 

“Isolate” on the l

abel. 

 
 
 
 
 
 
 
 
 
 
 
 
 

ISOL

+24V

AUTO

Yellow
LED

2K7

0V

EVAC

 

ISOL

AUTO

ELD

0V

EVAC

COM

 

A/I/E- Switch Wiring 

Figure A 

Isolate Indication via Spare Switch Pole 

Figure B 

Using Isolate Position to Generate Fault 

Figure C 

 

3.2  Background Music/Remote Paging 
 

An external audio source can be connected to the T-GEN MUSIC input, J9, for background music, external paging, etc.  
This source must have an isolated output, otherwise an audio isolating transformer, e.g. the ALIM9706 (part number 
PA0646), must be used.  Refer to LT0372 for the ALIM wiring arrangement. 
 
A background music loom adapter consisting of a 2 way plug with red (SIG) and black (GND) wires is supplied with the 
T-GEN. 

 
 
 
 
 
 
 
 

Remote paging (non-emergency) can be achieved by using the PA0688 microphone preamp board.  Refer to LT0371 for 
details.

 

 

3.3 Microphone  

 

An emergency PA microphone (part number ME0290) can be connected to J1 on the T-GEN. 

 
 
 
 
 
 
 

For a remote emergency PA microphone, refer to LT0371 for using a PA0688 microphone preamp. 

 

T-GEN 50 

Master 

Music             
J9 

 

Sound System 

 

SIG 

2.5Vrms max 

GND 

Mic Preamp 

(see LT0371)

 

 

Screened cable 

J1-1 MIC- 
J1-2 MIC+ 
J1-3 PTT  
J1-4 PTT

 

T-GEN 50 

MASTER 

A/I/E-               
 
0V

 

10k

 

ISOL

 

EVAC

 

AUTO

 

RED 
 
BLACK 

Содержание T-GEN 50

Страница 1: ...S These instructions apply to units with V1 70 software onwards Refer to LT0186 Issue 2 30 for instructions for earlier software versions A pre assembled Building Occupant Warning System BOWS that uti...

Страница 2: ...lic address This is activated when the microphone s PTT button is pressed while the A I E switch is in the Auto or Evac position Public address overrides Alert and Evac tones A remote microphone can b...

Страница 3: ...e Recorded Message OFF ON OFF Present ISO8201 keywords Msg 1 Msg1 Evacuate the building using the nearest fire exit OFF ON ON Don t Care TEST mode Msg2 Evacuate as directed x2 ON OFF OFF None Wail sou...

Страница 4: ...the end of the line If wiring on two branches then two 100k ELDs are used one on each branch The capacitors must be bipolar and their value should be 1 5uF per Watt of their speaker s load see below S...

Страница 5: ...esistor from the Isolate switch and blank off the word Isolate on the label ISOL 24V AUTO Yellow LED 2K7 0V EVAC ISOL AUTO ELD 0V EVAC COM A I E Switch Wiring Figure A Isolate Indication via Spare Swi...

Страница 6: ...mega 64 Mk3 4100ES 4 Switch SW4 ON for the Master T GEN Fit LK7 in Relay Position for all T GENs 5 FP1600 Omega 64 Mk3 boards have three 7 segment displays 6 ELD value depends upon Input type not fitt...

Страница 7: ...to enable Fault Relay Turn SW4 off 3 RRM must be inside FIP and wired to RESP IN 4 Connect wire from NC terminal of relay to S pin of supervision link Do not fit Sup link at all 5 3k3 ELD for MX4428 A...

Страница 8: ...L see Note 1 Sigma 5 FP1600 Mk3 Note 3 OMEGA 64 Mk3 Note 3 0V 3 7 Earth Connection The T GEN must be connected to the cabinet EARTH using either the EARTH terminal on the T GEN PCB located beside the...

Страница 9: ...upplied fitted to provide a complete functional unit A loom for power control and monitoring is factory fitted The loom is connectorised for direct use with MX1 The connector can be removed and the lo...

Страница 10: ...T0186 Issue 2 80 27 July 2012 Page 10 of 10 Manufactured Tyco Fire Protection Products Distributed by 17 Mary Muller Drive PO Box 19 545 by Christchurch New Zealand Tel 64 3 389 5096 Fax 64 3 389 5938...

Отзывы: