Note
With the following procedure, para-
meters
can only be scanned
but
not
modified
.
For modifying settings, see from
page 35.
Scanning parameters
Starting from the standard display,
activate the following switches and
keys:
1.
Set the rotary selector to
"MENU".
2.
xw
Select parameter: "Service
settings".
3.
d
Call up parameter 1 (Step
no. 1).
4.
d
until all parameters have
been displayed and the
standard display is shown
again.
Note
Parameter selection cannot be
reset as a whole. All individual
parameters must be confirmed in
sequence with
d
, to return to the
start, i.e. the standard display.
The standard display will be shown
again if no key is pressed for more
than 5 min.
Fixed parameters
No. Description
Possible va-
lues
Converted display value
12
Appliance type
180/300/400
Vitovent 180/300/400
13
Current throughput in m
3
/h 0 to 40
0 to 400 m
3
/h
14
Bypass function (status)
0, 1 and 2
0-closed, 1-open, 2-min ven-
tilation air
15
Outside air temperature
°C
-100 to +200
-100 to +100
16
Room air temperature in
°C
-100 to +100
-100 to +100
17
Current outside air flow
rate in m
3
/h
0 to 40
0 to 400 m
3
/h
18
Current extract air flow
rate in m
3
/h
0 to 40
0 to 400 m
3
/h
19
Current ventilation air
pressure in Pa
0 to 120
0 to 120 Pa
Remote control settings by contractors
(cont.)
33
Remote control settings
5692
762
GB
Содержание VITOVENT 300
Страница 44: ...Version 180 m3 h Parts list cont 44 Parts list 5692 762 GB...
Страница 46: ...Version 300 and 400 m3 h Parts list cont 46 Parts list 5692 762 GB...
Страница 47: ...List of control parameters 47 Commissioning service reports 5692 762 GB...
Страница 48: ...Commissioning report example 48 Commissioning service reports 5692 762 GB...