A
Slider aperture width
1.
Determine the width of the air inlet
using the intended flow rate and the
specified pressure drop from the
following diagram.
2.
Adjust the air inlet in accordance
with the calculated aperture width.
Note
Remove the grille to enable the
adjustment.
3.
Record the actual value in the com-
missioning report.
A
Slider aperture width [mm]
4.
Measure the air velocity with an
impeller air speed meter (see
page 20).
5.
Check the air flow rate in accor-
dance with the following table.
Further details regarding the individual steps
(cont.)
14
Commissioning, inspection, maintenance
5692
762
GB