A
Slot width [mm]
2.
Adjust the air inlet in accordance
with the calculated aperture width.
3.
Record the actual value in the com-
missioning report.
Setting the air flow directions
A
Directions of air flow
B
Scale range
C
Ceiling installation: Set to 1/A and
F/6
D
Ceiling installation: All set to 6
E
Wall installation: Set to C/D
Further details regarding the individual steps
(cont.)
16
Commissioning, inspection, maintenance
5692
762
GB