Adjusting the ventilation apertures
Ventilation aperture for wall integration (DN 100)
1.
Determine the width of the air inlet
using the intended flow rate and the
specified pressure drop from the
following diagram.
2.
Adjust the air inlet in accordance
with the calculated aperture width.
A
Number of apertures
3.
Record the actual value in the com-
missioning report.
Example:
Calculate the number of apertures at a
pressure drop of
Δ
p
s
= 20 Pa:
Air flow rate (acc.
to design):
q
v
= 27 m
3
/h
Number of aper-
tures:
6
Ventilation aperture for ceiling mounting (DN 100)
Note
&
By twisting sector plate
B
the
direction of the fixed air outlet angle
of 180° can be determined (e.g.
installation near walls).
&
Removing sector plate
B
lets the
air exit evenly at an angle of 360°
(e.g. installation at the centre of the
room).
Further details regarding the individual steps
(cont.)
10
Commissioning, inspection, maintenance