62
5797 340 - 01
Vitoflex 300-RF Installation & Operating
Parameters
Heating Circuit 3
“Temperatures” tab
Parameters
Description
Setting in
Setting
range
Default
value
“Operating mode”
Displays the set operating mode for heating
--
--
--
“Operating status”
Displays the current operating state for heating
--
--
--
“Set flow at +10°C”
Set supply temperature at plus 10°C (18°F) outside
temperature
(°F)
°C
(68 to 194)
20 to 90
(104)
40
“Set flow at -10°C”
Set supply temperature at less 10°C (18°F) (outside
temperature
(°F)
°C
(68 to 194)
20 to 90
(122)
50
“Set value, heating curve” Displays the current set temperature
--
--
--
“Minimum flow”
Minimum set supply temperature
(°F)
°C
(68 to 201)
(20 to 94)
(86)
(30)
“Maximum flow”
Maximum set supply temperature
(°F)
°C
(70 to 203)
21 to 95
(158)
70
“Night setback”
Temperature value by which the set supply
temperature is reduced outside the heating periods
(°F)
°C
(32 to 68)
0 to 20
(45)
7
“Set valve runtime”
Valve runtime from 0% to 100%
seconds
200 to 500
140
Note:
For “Heating periods” tab, see page 60