33
5797 340 - 01
Vitoflex 300-RF Installation & Operating
Mechanical
Equipment to be supplied by the installing heating
contractor:
- PDP pressure relief valve drain pipe
- DCW Cold water inlet, min. 36 psi (2.5 bar), max.
51 psi (3.5 bar)
- AV Air separator / vent
- ExP Expansion tank closed;
- for safety heat exchanger required (size according
to volume of safety heat exchanger loops and volume
of piping)
- for heating system (optional)
- WSL Water supply line for safety heat exchanger
- SDP Safety heat exchanger drain pipe
- SRL System return line to the boiler from the system
- SSL System supply line from the boiler to the system
- BPL Bypass line
- BR Boiler return
- BS Boiler supply
Piping and Installation of Safety Devices
(continued)
Note:
To reliably prevent boiler corrosion caused
by condensation of flue gases, the boiler return
temperature must not under any circumstances
be below 150°F (65°C).
A Viessmann sized boiler pump with a boiler
3-way mixing valve are provided according to the
tables below. The boiler circuit should be designed
that the temperature difference between the supply
and the return temperature is equal to or less than
∆
t 27°F (15°C).
The expansion tank has to be connected to the
boiler without any shut-offs.
Safety equipment included in the scope of supply provided
by Viessmann:
-
M 20
Boiler pump
-
Y 20
Boiler 3-way mixing valve
-
PRV
Pressure relief valve, pressure set to 30 or 60 psi
-
TS2430
Thermal safety flush valve R ¾ in., approved
component; special-purpose, designed for opening
at a temperature of 122-248°F (50-120°C),
(safety heat exchanger loop built into the boiler).
The Vitoflex 300-RF 150 to Vitoflex 300-RF 300 have
one safety heat exchanger loop and require one thermal
safety flush valve. The Vitoflex 300-RF 400 and
Vitoflex 300-RF 540, have two safety heat exchanger
loops and require one thermal safety flush valve.
-
LWCO
Low water cut-off
-
PG
Pressure gauge
-
TG
Temperature gauge (thermometer)
-
SHE
Safety heat exchanger, water volume 1.1 USG
(4.2 L) per loop, NPTM
b
in.
Design recommendation:
Thermal safety flush valve
Boiler
Model
RF-
Thermal safety
flush valve
TS-2430
(Quantity)
Water through-put
required at
36 psi (2.5 bar)
L/h GPM
Supply
line
WSL
Drain pipe
SDP
2
150
1
915 4
R
c
in.
R 1 in.
220
1
1230 5.4
R
c
in.
R 1 in.
300
1
1500 6.6
R
c
in.
R 1 in.
400
1
1880 8.3
R
c
in.
R 1 in.
540
1
2226 10
R
c
in.
R 1 in.
1
Threaded connection for supply line
2
Length of the drain pipe up to 13 ft. (4.0 m)
Pressure relief valve
Boiler
Model
RF-
Pressure relief
valve Conbraco
1
30 psi or 60 psi
Pressure relief
valve drain pipe
PDP
2
30 psi or 60 psi
150
1 in.
c
in. 1
a
in. 1 in.
220
1 in.
c
in. 1
a
in. 1 in.
300
1
a
in. 1 in. 1
b
in. 1
a
in.
400
1
a
in. 1
a
in. 1
b
in. 1
b
in.
540
1
b
in. 1
a
in. 2 in. 1
b
in.