51
5797 340 - 01
Vitoflex 300-RF Installation & Operating
Parameters
Charging
(continued)
Parameters
Description
Setting in
Setting
range
Default
value
“Emergency mode”
“Pulse”
If the runtime monitoring function for the transverse
screw conveyor is triggered, it is assumed that bridging
has occurred in the trough. The discharge will then
run using the times specified here until the container is
empty or the light barrier is clear again.
For definition of “Pulse/Pause” see above
seconds
0 to 100
5
“Pause”
0 to 500
5
“Runtime, transverse screw conveyor, maximum”
“Delay ON”
If the maximum runtime of the transverse screw conveyor
has been exceeded, the container or pushrod discharge
will operate with the pause and pulse times specified
under “Emergency mode”.
For definition of “Delay ON” see page
seconds
0 to 1000
80
Auto and Manual
selection fields
- Auto (Automatic): If there is more than one container, the system changes over to the next
container if a fault occurs or the container is empty.
- Manual 1, 2 or 3: Container 1, 2 or 3 is in manual mode. The relevant container is used.
“Delay, empty
message”
Delay due to empty message
In the event of an empty message, the system changes
over to the next available container. If no further containers
are available, a controlled system shutdown is performed.
seconds
0 to 800
300
“Cycle control”
“Delay ON”
For definition of “Delay ON” see above
seconds
0 to 50
2
“Pulse”
For definition of “Pulse” see above
seconds
0 to 100
5
“Pause”
For definition of “Pause” see above
seconds
0 to 500
5
“Pendulum screw conveyor”
“Delay ON”
For definition of “Delay ON” see above
seconds
0 to 20
5
“Pulse”
For definition of “Pulse” see above
seconds
0 to 100
5
“Pause”
For definition of “Pause” see above
seconds
0 to 500
5
“Preferred direction”
“Preferred direction
ON”
If “Preferred direction” is ON, the discharge runs to the
right by preference (without reversing).
For definition of “Delay ON/OFF” see above
seconds
“ON”/”OFF”
“OFF”
“Preferred direction
OFF”
“Reversing interval”
“Delay ON”
If “Preferred direction” is OFF, the pendulum screw
conveyor changes rotational direction after this time has
elapsed.
For definition of “Delay ON” see above
seconds
0 to 1000
240