58
5797 340 - 01
Vitoflex 300-RF Installation & Operating
Buffer Tank
“Temperatures” tab
Parameters
Description
Setting in
Setting
range
Default
value
“Operating mode”
Set operating mode of buffer tank
--
“ Köb”
“ Köb”
“Boiler start at
sensor”
Setting specifies which sensor the boiler should start at
--
“ B28.2”
“ B28.2”
“Tank temperature
at +5°C”
Set tank temperature at plus 5°C (9°F) outside
temperature
(°F)
°C
(86 to 201)
30 to 94
(167)
75
“Tank temperature
at -15°C”
Set tank temperature at less 15°C (27°F) outside
temperature
(°F)
°C
(88 to 203)
31 to 95
(185)
85
“Tank temperature,
minimum”
Minimum set tank temperature
(°F)
°C
(122 to 201)
50 to 94
(167)
75
“Tank temperature,
maximum”
Maximum set tank temperature
(°F)
°C
(124 to 203)
51 to 95
(194)
90
“Outside
temperature”
Displays the current outside temperature
(°F)
°C
--
--
--
--
“Tank charging,
to sensor”
Setting specifies to which sensor the boiler should
charge the heating water buffer tank
--
“ B28.4”
“ B28.4”
“Tank charging,
to temperature”
Setting specifies the temperature to which the boiler
should charge the heating water buffer tank
(°F)
°C
(167 to 194)
75 to 90
(176)
80
Parameters