60
Adjust values for Vitovent 200-W/300-C/300-W if necessary
Parameter
Setting
"Ventilation"
Ó
"Set room temperature C108"
Max. 4 K higher or lower than
"Stand-
ard room temperature 2000"
(adjust-
ment value: 1
≙
0.1 °C)
"Background ventilation C109"
Subject to sizing
Ventilation unit service instruc-
tions
"Reduced ventilation C10A"
"Standard ventilation C10B"
"Intensive ventilation C10C"
"Background ventilation, second fan duct C189"
(Vitovent 200-W only)
"Reduced ventilation, second fan duct C18A"
(Vitovent 200-W
only)
"Standard ventilation, second fan duct C18B"
(Vitovent 200-W
only)
"Intensive ventilation, second fan duct C18C"
(Vitovent 200-W
only)
Parameters for ventilation with Vitovent 300-F
Parameter
Setting
"Ventilation"
Ó
"Vitovent enable 7D00"
"1"
Vitovent 300-F
Further enabling for Vitovent 300-F if necessary
Parameter
Setting
"Ventilation"
Ó
"Enable preheater bank electric 7D01"
"1"
"Enable reheater bank hydraulic 7D02"
"1"
"Enable humidity sensor 7D05"
"1"
"Enable CO2 sensor 7D06"
"1"
"Type of heat exchanger 7D2E"
"0"
Countercurrent heat exchanger
"1"
Enthalpy heat exchanger
Adjust values for Vitovent 300-F if necessary
Parameter
Setting
"Ventilation"
Ó
"Set room temperature 7D08"
"100"
to
"300"
(
≙
10 to 30 °C)
"Flow rate reduced ventilation 7D0A"
Subject to sizing
Ventilation unit service instruc-
tions
"Flow rate nominal ventilation 7D0B"
"Flow rate intensive ventilation 7D0C"
Commissioning, inspection, maintenance
Commissioning the system
(cont.)
6153640
Содержание VITOCAL 300-G
Страница 12: ...12 Removing the front panel 3 2 1 4 Fig 3 Installation sequence Siting the heat pump 6153640 Installation...
Страница 14: ...14 5 4 6 Fig 5 7 Fig 6 Installation sequence Siting the heat pump cont 6153640 Installation...
Страница 20: ...20 Opening the wiring chamber 1 2 Fig 10 Installation sequence Electrical connection cont 6153640 Installation...
Страница 22: ...22 6x X X 7 4 8 5 6 Fig 13 10 9 11 Fig 14 Installation sequence Electrical connection cont 6153640 Installation...