30
Plug
sXS
Clamps
Function
Explanation
222.1
Control of mixer motor for external
heat generator
Mixer CLOSE signal
Connection values:
■
Output: 10 W
■
Voltage: 230 V~
■
Max. switching current: 0.2(0.1) A
222.2
Control of mixer motor for external
heat generator
Mixer OPEN signal
Connection values:
■
Output: 10 W
■
Voltage: 230 V~
■
Max. switching current: 0.2(0.1) A
222.3
222.4
Control of external heat generator
and high limit safety cut-out (on site,
max. 70 °C), to simultaneously switch
off the following components:
■
Secondary pump
■
External heat generator
Floating contact
Note
■
The switching contact is a floating N/O contact that is
closed when a heat demand is issued.
■
Never route extra low voltage (ELV) via this contact.
For that, a relay must be fitted on site.
■
The boiler water temperature sensor in the external
heat generator (plug F20) must capture the average
temperature of the external heat generator.
Connection values (contact load):
■
Voltage: 230 V~
■
Max. switching current: 4(2) A
Connect the high limit safety cut-out:
See the following chapter.
Installation sequence
Electrical connection
(cont.)
6153640
Installation
Содержание VITOCAL 300-G
Страница 12: ...12 Removing the front panel 3 2 1 4 Fig 3 Installation sequence Siting the heat pump 6153640 Installation...
Страница 14: ...14 5 4 6 Fig 5 7 Fig 6 Installation sequence Siting the heat pump cont 6153640 Installation...
Страница 20: ...20 Opening the wiring chamber 1 2 Fig 10 Installation sequence Electrical connection cont 6153640 Installation...
Страница 22: ...22 6x X X 7 4 8 5 6 Fig 13 10 9 11 Fig 14 Installation sequence Electrical connection cont 6153640 Installation...