78
1.
8x
B
A
2.
!
Please note
A short circuit between the mag-
nesium anode and internal indi-
rect coil increases the protective
effect of the magnesium anode
and leads to corrosion damage
on the DHW cylinder.
Before inserting the electrical
cables, measure the resistance
between terminals
A
and
B
. If
the resistance is significantly less
than infinity, check whether the
magnesium anode is touching
the internal indirect coil.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)