20
■ In regions with prolonged cold sea-
sons (e.g. in Germany), provide an
electric supplementary heating facility
(accessory) for the condensate pan.
■ For insulation of structure-borne noise
and vibrations between the building
and the external unit, consider the fol-
lowing measures:
– When cable entry is
above
ground
level, fit pipe bends as anti-vibration
mounts in refrigerant lines (see
"Connecting refrigerant lines").
– Route electrical cables/leads
between the internal and external
units free of stress.
– Installation only on walls with high
weight per area (> 250 kg/m
2
), in
other words not on lightweight walls,
roof structures etc.
– When mounting the unit on the floor,
use only the rubber mounts sup-
plied; for wall mounting use the anti-
vibration mounts supplied with the
wall mounting bracket set; never use
additional anti-vibration mounts,
springs, rubber buffers etc.
Weights of the external units
Type AWT-AC
Weight in kg
221.A04
43
221.A07
66
221.A10
110
221.A13
110
Installation sequence
Installing the external unit
(cont.)
5600 950 GB
Содержание Vitocal 222-S
Страница 26: ...26 7 8 6 P301 P501 P303 P302 F6 Installation sequence Installing the internal unit cont 5600 950 GB...
Страница 27: ...27 10 9 11 Installation sequence Installing the internal unit cont 5600 950 GB Installation...
Страница 28: ...28 15 2x 16 17 2x 12 14 18 13 X20 Installation sequence Installing the internal unit cont 5600 950 GB...
Страница 29: ...29 2x 4x 6x 4x 22 21 20 19 Installation sequence Installing the internal unit cont 5600 950 GB Installation...
Страница 89: ...89 Opening programming unit 2 2x 1 3 Troubleshooting Repairs 5600 950 GB Service...
Страница 90: ...90 Removing cover from programming unit if necessary 5 4 4x Troubleshooting Repairs cont 5600 950 GB...
Страница 91: ...91 Overview of internal components Internal unit Troubleshooting Repairs cont 5600 950 GB Service...
Страница 142: ...142 5600 950 GB...
Страница 143: ...143 5600 950 GB...