121
Setting and test values
Set value
Commission-
ing
Testing the external heating circuit pumps
Circulation pump type
Circulation pump stage
Overflow valve setting
Primary circuit commissioning
Air inlet temperature
°C
Air discharge temperature
°C
Temperature differential ΔT:
Secondary circuit flow temperature = 35 °C
at air inlet temperature
≤
15 °C
K
4 to 8
Secondary circuit flow temperature = 35 °C
at air inlet temperature > 15 °C
K
4 to 13
Testing the mixer, heat pump and cylinder heating
Checked under the following conditions:
Room temperature
°C
Outside temperature
°C
Temperature
"Cylinder temp. top"
con-
stant?
Yes (±1 K)
Secondary circuit flow temperature
°C
rising
from
to
Temperature differential ΔT
"Flow temp. secondary"
/
"Return temp.
sec."
6 to 8 K
Control parameter report
For a description of parameters, see
service instructions for Vitotronic 200
heat pump control unit.
Commissioning/service reports
Hydraulic parameter report
5600 950 GB
Service
Содержание Vitocal 222-S
Страница 26: ...26 7 8 6 P301 P501 P303 P302 F6 Installation sequence Installing the internal unit cont 5600 950 GB...
Страница 27: ...27 10 9 11 Installation sequence Installing the internal unit cont 5600 950 GB Installation...
Страница 28: ...28 15 2x 16 17 2x 12 14 18 13 X20 Installation sequence Installing the internal unit cont 5600 950 GB...
Страница 29: ...29 2x 4x 6x 4x 22 21 20 19 Installation sequence Installing the internal unit cont 5600 950 GB Installation...
Страница 89: ...89 Opening programming unit 2 2x 1 3 Troubleshooting Repairs 5600 950 GB Service...
Страница 90: ...90 Removing cover from programming unit if necessary 5 4 4x Troubleshooting Repairs cont 5600 950 GB...
Страница 91: ...91 Overview of internal components Internal unit Troubleshooting Repairs cont 5600 950 GB Service...
Страница 142: ...142 5600 950 GB...
Страница 143: ...143 5600 950 GB...