Heating program changeover
Coding
No changeover
91:0
Heating circuit without mixer A1
91:1
Heating circuit with mixer M2
91:2
Heating circuit without mixer and heating circuit with mixer 91:3
You can select which direction the
heating program changes over in cod-
ing address "D5":
Heating program changeover
Coding
Changeover towards "Permanently reduced" or "Perma-
nent standby" mode (subject to the selected set value)
d5:0
Changeover towards "Constant heating mode"
d5:1
The duration of the heating program
changeover can be adjusted in coding
address "F2":
Heating program changeover
Coding
No heating program changeover
F2:0
Duration of the heating program changeover 1 to 12 hours
F2:1 to
F2:12
The heating program changeover
stays enabled for as long as the con-
tact remains closed, but at least as
long as the duration selected in cod-
ing address "F2".
External blocking
The "External blocking" function is
connected via input "
aVD
".
In coding address "32" you can select
the influence the "Ext. blocking" sig-
nal should have on the connected cir-
culation pumps.
External demand
The "External demand" function is
connected via input "
aVD
".
Control functions
(cont.)
81
Function description
5692
745
GB
Содержание VC3
Страница 91: ...Internal extensions H1 and H3 A5 and A9 Connection and wiring diagram internal cont 91 Designs 5692 745 GB ...
Страница 96: ...Parts lists cont 96 Parts lists 5692 745 GB ...
Страница 97: ...Parts lists cont 97 Parts lists 5692 745 GB ...
Страница 98: ...Parts lists cont 98 Parts lists 5692 745 GB ...
Страница 99: ...Parts lists cont 99 Parts lists 5692 745 GB ...
Страница 100: ...Parts lists cont 100 Parts lists 5692 745 GB ...
Страница 101: ...Parts lists cont 101 Parts lists 5692 745 GB ...
Страница 103: ...Service Service Service Service Commissioning service reports cont 103 Commissioning service reports 5692 745 GB ...
Страница 109: ...109 5692 745 GB ...
Страница 110: ...110 5692 745 GB ...
Страница 111: ...111 5692 745 GB ...