Coding in the delivered condition
Possible change
Boiler circuit, mixer circuit
A4:0
With frost protection
A4:1
No frost protection, ad-
justment only possible if
coding address "A3: -9"
has been selected.
Note
When selecting a value
below 1 °C, there is a risk
of pipes outside the ther-
mal envelope of the
building being damaged
by frost. The standby
mode, in particular,
should be taken into con-
sideration, e.g. during
holidays.
A5:5
With heating circuit
pump logic function
(economy circuit): Heat-
ing circuit pump OFF if
outside temperature
(AT) is 1 K higher than
the set room tempera-
ture (RT
Set
)
AT > RT
set
+ 1 K
A5:0
Without heating circuit
pump logic function
A5:1
to
A5:15
With heating circuit pump
logic function: Heating
circuit pump OFF, if (see
the following table)
Parameter address
A5:...
With heating circuit pump logic function: Heating
circuit pump OFF, if
1
AT > RT
set
+ 5 K
2
AT > RT
set
+ 4 K
3
AT > RT
set
+ 3 K
4
AT > RT
set
+ 2 K
5
AT > RT
set
+ 1 K
6
AT > RT
set
7
to
AT > RT
set
- 1 K
15
AT > RT
set
- 9 K
Code 2
(cont.)
50
Coding
5692
745
GB
Содержание VC3
Страница 91: ...Internal extensions H1 and H3 A5 and A9 Connection and wiring diagram internal cont 91 Designs 5692 745 GB ...
Страница 96: ...Parts lists cont 96 Parts lists 5692 745 GB ...
Страница 97: ...Parts lists cont 97 Parts lists 5692 745 GB ...
Страница 98: ...Parts lists cont 98 Parts lists 5692 745 GB ...
Страница 99: ...Parts lists cont 99 Parts lists 5692 745 GB ...
Страница 100: ...Parts lists cont 100 Parts lists 5692 745 GB ...
Страница 101: ...Parts lists cont 101 Parts lists 5692 745 GB ...
Страница 103: ...Service Service Service Service Commissioning service reports cont 103 Commissioning service reports 5692 745 GB ...
Страница 109: ...109 5692 745 GB ...
Страница 110: ...110 5692 745 GB ...
Страница 111: ...111 5692 745 GB ...