Coding in the delivered condition
Possible change
77 :1
LON subscriber number 77 :2
to
77 :99
LON subscriber number,
adjustable from 1 to 99:
1 - 4 = Boiler
5 = Cascade
10 - ... = Vitotronic 200-H
99 = Vitocom
Note
Allocate each number
only
once.
79:1
Control unit is fault
manager
79:0
Control unit is not fault
manager
7b:1
Send time via LON
7b:0
Do not send time via LON
7F:1
Detached house
7F:0
Apartment block
Separate adjustment of
holiday program and time
program for DHW heat-
ing, as option
80:1
With 5 s delay for fault
message; message is
displayed if fault is pre-
sent for at least 5 s
80:0
Without time delay
80:2
to
80:199
Time delay adjustable
from 10 to 995; 1 step =
5 s
81:1
Automatic summer/win-
ter time changeover
81:0
Manual summer/winter
time changeover
81:2
Radio clock module is
automatically detected
81:3
Accept time via LON
88 :0
Temperatures are dis-
played in °C (Celsius)
88 :1
Temperatures are dis-
played in
°F (Fahrenheit)
90:128
Time constant for calcu-
lating adjusted outside
temperature 21.3 h
90:0
to
90:199
Fast (low values) or slow
(high values) matching of
the flow temperature,
subject to the set value
when the outside tem-
perature changes;
1 step = 10 min
Code 2
(cont.)
47
Coding
5692
745
GB
Содержание VC3
Страница 91: ...Internal extensions H1 and H3 A5 and A9 Connection and wiring diagram internal cont 91 Designs 5692 745 GB ...
Страница 96: ...Parts lists cont 96 Parts lists 5692 745 GB ...
Страница 97: ...Parts lists cont 97 Parts lists 5692 745 GB ...
Страница 98: ...Parts lists cont 98 Parts lists 5692 745 GB ...
Страница 99: ...Parts lists cont 99 Parts lists 5692 745 GB ...
Страница 100: ...Parts lists cont 100 Parts lists 5692 745 GB ...
Страница 101: ...Parts lists cont 101 Parts lists 5692 745 GB ...
Страница 103: ...Service Service Service Service Commissioning service reports cont 103 Commissioning service reports 5692 745 GB ...
Страница 109: ...109 5692 745 GB ...
Страница 110: ...110 5692 745 GB ...
Страница 111: ...111 5692 745 GB ...