Adjusting the air volume (static burner pressure)
1.
Start the boiler.
2.
Remove plug
A
from the test port.
3.
Connect the U-shaped pressure
gauge to test port
A
.
4.
Press
K
and
F
simultaneously
until
"Speed stage 1"
and a value
between 1 and 255 are displayed.
5.
Change the value with
a
/
b
until
the static burner pressure dis-
played by the U-shaped pressure
gauge and the CO
2
flue gas con-
tent correspond to the values in the
table on page 15.
6.
Confirm the set value with
d
.
Note
The control unit changes automati-
cally to burner stage 2. The display
shows
"Speed stage 1 + 2 "
and a
value between 1 and 255.
7.
Repeat steps 4 and 5 for burner
stage 2.
8.
Check the set values.
9.
Seal test connector
A
again with
the previously removed plug.
Note
Do
not
seal the connector next to
test connector
A
.
Further details regarding the individual steps
(cont.)
17
Commissioning, inspection, maintenance
5692
745
GB
Содержание VC3
Страница 91: ...Internal extensions H1 and H3 A5 and A9 Connection and wiring diagram internal cont 91 Designs 5692 745 GB ...
Страница 96: ...Parts lists cont 96 Parts lists 5692 745 GB ...
Страница 97: ...Parts lists cont 97 Parts lists 5692 745 GB ...
Страница 98: ...Parts lists cont 98 Parts lists 5692 745 GB ...
Страница 99: ...Parts lists cont 99 Parts lists 5692 745 GB ...
Страница 100: ...Parts lists cont 100 Parts lists 5692 745 GB ...
Страница 101: ...Parts lists cont 101 Parts lists 5692 745 GB ...
Страница 103: ...Service Service Service Service Commissioning service reports cont 103 Commissioning service reports 5692 745 GB ...
Страница 109: ...109 5692 745 GB ...
Страница 110: ...110 5692 745 GB ...
Страница 111: ...111 5692 745 GB ...