4.
Secure Allen screw
B
of the rifling
facility. Check nozzle gap "a".
!
Please note
An incorrectly adjusted noz-
zle gap "a" can result in irre-
gular operation of the burner
and even a fault shutdown.
Rated output
kW
12.9/19.3
16.1/23.5
19.3/28.9
Nozzle gap "a"
(see page 19)
mm
3.0
+0.2/-0.3
1.5
+0.2/-0.3
1.5
+0.2/-0.3
Cleaning and replacing the oil pump filter, if required
Oil pump; make: Danfoss, type BFP 52
A
Filter plug
B
O-ring (replace)
C
Filter (replace)
Further details regarding the individual steps
(cont.)
20
Commissioning, inspection, maintenance
5692
745
GB