Coding in the delivered condition
Possible change
Boiler circuit, mixer circuit
A0:0
Without remote control
A0:1
With Vitotrol 200 (auto-
matic recognition)
A0:2
With Vitotrol 300 (auto-
matic recognition)
A3:2
Outside temperature
below 1 °C: Heating cir-
cuit pump ON
Outside temperature
above 3 °C: Heating cir-
cuit pump OFF
Note
When selecting a value
below 1 °C, there is a
risk of pipes outside the
thermal envelope of the
building being damaged
by frost. The standby
mode, in particular,
should be taken into
consideration, e.g. dur-
ing holidays.
A3:-9
to
A3:15
Heating circuit pump ON/
OFF (see the following
table)
Parameter
Heating circuit pump
Address A3:...
ON at
OFF at
-9
-10 °C
-8 °C
-8
-9 °C
-7 °C
-7
-8 °C
-6 °C
-6
-7 °C
-5 °C
-5
-6 °C
-4 °C
-4
-5 °C
-3 °C
-3
-4 °C
-2 °C
-2
-3 °C
-1 °C
-1
-2 °C
0 °C
0
-1 °C
1 °C
1
0 °C
2 °C
2
to
1 °C
to
3 °C
15
14 °C
16 °C
Code 2
(cont.)
49
Coding
5692
745
GB
Содержание VC3
Страница 91: ...Internal extensions H1 and H3 A5 and A9 Connection and wiring diagram internal cont 91 Designs 5692 745 GB ...
Страница 96: ...Parts lists cont 96 Parts lists 5692 745 GB ...
Страница 97: ...Parts lists cont 97 Parts lists 5692 745 GB ...
Страница 98: ...Parts lists cont 98 Parts lists 5692 745 GB ...
Страница 99: ...Parts lists cont 99 Parts lists 5692 745 GB ...
Страница 100: ...Parts lists cont 100 Parts lists 5692 745 GB ...
Страница 101: ...Parts lists cont 101 Parts lists 5692 745 GB ...
Страница 103: ...Service Service Service Service Commissioning service reports cont 103 Commissioning service reports 5692 745 GB ...
Страница 109: ...109 5692 745 GB ...
Страница 110: ...110 5692 745 GB ...
Страница 111: ...111 5692 745 GB ...