18
Cleaning the burner
B
A
1.
Remove the connecting cables from
fan
B
.
2.
Remove the fan.
3.
Clean the fan casing and impeller.
4.
For severe fan contamination (dust,
fluff), remove the ignition, ionisation
and control cables from the burner
door, then remove and clean air col-
lector casing
A
.
Fitting the burner
B
A
1.
Fit air collector casing
A
to the boiler
door.
2.
Install fan
B
.
3.
Connect the ignition and ionisation
cables.
4.
Fit the control cables to the boiler
door.
5.
Fit the gas supply pipe.
Danger
Escaping gas leads to a risk of
explosion.
Check all fittings for gas tight-
ness.
6.
Secure the gas train cables to the gas
pipe.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)