33
Internal system fault
Internal system faults are created if a perfect program sequence can no longer be
guaranteed.
Fault code System characteris-
tics
Cause
Measures
01 and 02,
04 to 15,
70 to 79,
7A, FF
Fault in burner con-
trol unit area
Internal system
fault
Replace burner control
unit
FF
Fault in burner con-
trol unit area
EEPROM
Have system tested for
EMC interference
Faults without fault display
Fault
Cause
Measures
Combustion faults
through pulsation
Excessive gas
throughput
Adjust gas throughput in accord-
ance with rated boiler output
Air shortage or
excess
Adjust gas throughput in accord-
ance with rated boiler output
Condensate banked
up in flue gas system
Check condensate drain
Incorrect flue gas
draught
Check flue gas draught
Burner restarts and
switches off after safety
time has expired
Cores "L1" and "N" at
mains terminals of
control unit inter-
changed
Check power supply and exchange
cores
CO is formed or burner
very sooty
Air shortage or
excess
Adjust correctly. Check installation
room ventilation
Insufficient draught in
flue gas system
Check flue gas system
CO
2
content too low
Incorrect setting
Check that burner has been set to
correct gas type; change gas
restrictor if required (see from
page 7).
Adjust burner in accordance with
the details on page 12.
Troubleshooting
Diagnosis
(cont.)
5692 488 GB