Checking the gas type
1.
Determine the gas type and Wobbe
index (Wo) from your gas supply util-
ity.
■ With the
natural gas E setting
, the
boilers can be operated in the
Wobbe index range 12.0 to
16.1 kWh/m
3
(43.2 to 58.0 MJ/m
3
).
■ With the
natural gas LL setting
,
the boilers can be operated in the
Wobbe index range 10.0 to
13.1 kWh/m
3
(36.0 to 47.2 MJ/m
3
)
(not in
a
and
c
).
2.
In the delivered condition, the burner
is set up for natural gas E. If required,
convert the burner to the other gas
type in accordance with details provi-
ded by your gas supply utility (see
page 7).
3.
Record the gas type in the report (on
page 45).
Conversion to natural gas LL
(not in
a
and
c
)
C
B
A
0
1.
Close the gas shut-off valve.
0
2.
Switch OFF the control unit ON/OFF
switch.
0
3.
Switch OFF the main isolator (out-
side the installation room) or the
power supply and prevent unauthor-
ised reconnection.
0
4.
Release the cable fixings on the gas
pipe.
0
5.
Release compression fittings
A
and
C
remove the gas pipe.
0
6.
Unscrew gas restrictor
B
.
0
7.
Take gas restrictor
B
for natural
gas LL from the pack supplied and
screw on (for diameter see table on
page 46).
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)