49
Display
Action
Ignition
No
Fault EE
Check ignition mod-
ule (control voltage
230 V across plugs
"X2.1" and "X2.2").
Check the gas sup-
ply.
Yes
Gas train opens
No
Fault EE
Check the gas train
(230 V control volt-
age) and gas supply
pressure
Yes
Ionisation current builds
Symbol
A
No
Fault EE
Check the ionisation
electrode adjustment
and check the gas
line for airlocks.
Yes
Burner in operation
Yes
No
Burner shuts
down below the
following temper-
atures and re-
starts immediate-
ly:
Set flow temper-
ature, secondary
circuit
Desorption tem-
perature
No
Check the flue sys-
tem for tightness
(flue gas recircula-
tion); check the gas
flow pressure
Commissioning, inspection, maintenance
Function sequence and possible faults
(cont.)
5678 044 GB