39
Danger
Flue gas escaping from the siphon can cause
potentially fatal carbon monoxide poisoning.
Always fill the siphon with water
before
commis-
sioning.
B
A
C
2.
4.
3.
Fig. 26
A
Retaining clip
B
Filler pipe
C
Lute
1.
Pivot control unit forwards and remove cover
panel.
5.
Fill trap with water and refit.
6.
Check that the condensate hoses are connected
correctly to the siphon and heat exchangers.
Note
Route the drain hose without any bends and with a
constant fall.
7.
Remount the cover panel.
8.
Secure the control unit back in the operating posi-
tion.
Switching on the power supply and the ON/OFF switch
Commissioning, inspection, maintenance
Filling the trap with water
5678 044 GB