71
■
At coding level 2, all codes are accessible, including
the codes at coding level 1.
■
Codes that have no function, either due to the sys-
tem equipment level or due to the setting of other
codes, are not displayed.
■
Heating systems with 1 heating circuit without mixer
and 1 or 2 heating circuits with mixer:
In the following, the heating circuit without mixer is
referred to as
"Heating circuit 1"
and the heating
circuits with mixer as
"Heating circuit 2"
and
"Heat-
ing circuit 3"
.
If the heating circuits have been given individual des-
ignations, the selected designation and
"HC1"
,
"HC2"
or
"HC3"
appear instead.
■
For code groups, see page 63.
Service menu:
1. Press
OK
and
simultaneously for approx. 4 s.
2. Press
OK
and simultaneously for approx. 4 s.
3.
"Coding level 2"
4. / for the group of the required coding address
5. / for the required coding address
6. / for the required value in line with the tables
below
Note
The system exits the service menu automatically after
30 min.
Resetting all codes to their delivered condition (reset)
Select
"Standard setting"
in coding level 2.
Note
This also resets codes at coding level 1.
Codes for sorption mode and natural heat source
in the "Process" group:
A reset causes sorption mode to be deactivated (code
"14:0") and the natural heat source selection (code
"1A:0") to be reset. The codes must be re-entered.
"General"
Select
"General"
(see page 71).
Coding
Coding in the delivered condition
Possible change
00:1
System version 1:
One heating circuit without mixer
A1 (heating circuit 1), without DHW
heating
00:2
to
00:10
For system schemes, see the follow-
ing table:
Value, ad-
dress 00: ...
Description
2
1 heating circuit without mixer A1 (heating circuit 1), with DHW heating (code is set automatical-
ly)
3
1 heating circuit with mixer M2 (heating circuit 2), without DHW heating
4
1 heating circuit with mixer M2 (heating circuit 2), with DHW heating
5
1 heating circuit without mixer A1 (heating circuit 1) and 1 heating circuit with mixer M2
(heating circuit 2), without DHW heating (code is set automatically)
6
1 heating circuit without mixer A1 (heating circuit 1) and 1 heating circuit with mixer M2
(heating circuit 2), with DHW heating (code is set automatically)
7
1 heating circuit with mixer M2 (heating circuit 2) and 1 heating circuit with mixer M3
(heating circuit 3), without DHW heating
8
1 heating circuit with mixer M2 (heating circuit 2) and 1 heating circuit with mixer M3
(heating circuit 3), with DHW heating
Code 2
Calling up coding level 2
5678 044 GB
Codes
Содержание D2RA
Страница 34: ...34 1 3 4 2 2x 5 5 Fig 24 Installation sequence Fitting the front panels 5678 044 GB Installation ...
Страница 113: ...113 Maintenance Checking the Vitotronic 200 H accessories cont 5678 044 GB Maintenance ...
Страница 126: ...126 0004 0002 0004 0002 0001 0001 0002 0004 0002 0003 Fig 79 Parts lists Sorption module 5678 044 GB Components ...
Страница 133: ...133 Parts lists Sorption module hydraulics cont 5678 044 GB Components ...
Страница 136: ...136 0001 0002 0003 0004 0005 Fig 83 Parts lists Miscellaneous 5678 044 GB Components ...
Страница 163: ...163 5678 044 GB ...