61
Note
The same subscriber number must
not
be allocated
twice within the LON.
Only one Vitotronic
may be programmed as fault
manager.
All coding addresses in the table are listed in the "General" group.
Boiler control unit
Vitotronic 200-H
Vitotronic 200-H
Vitocom
LON
LON
LON
Subscriber no. 1
Code "77:1"
Subscriber no. 10
Code "77:10"
Subscriber no. 11
Set
code "77:11".
Subscriber no. 99
Control unit is fault manager.
Code "79:1"
Control unit is not fault man-
ager.
Code "79:0"
Control unit is not fault man-
ager.
Code "79:0"
Device is fault man-
ager.
Control unit transmits the
time.
Code "7b:1"
Control unit receives the
time.
Set
code "81:3".
Control unit receives the
time.
Set
code "81:3".
Device receives the
time.
Control unit sends outside
temperature.
Set
code "97:2".
Control unit receives outside
temperature.
Set
code "97:1".
Control unit receives outside
temperature.
Set
code "97:1".
—
Viessmann system number.
Code "98:1"
Viessmann system number.
Code "98:1"
Viessmann system number.
Code "98:1"
—
LON subscriber fault monitor-
ing.
Code "9C:20"
LON subscriber fault moni-
toring.
Code "9C:20"
LON subscriber fault moni-
toring.
Code "9C:20"
—
Carrying out a LON subscriber check
The subscriber check is used to test communication
with the system devices connected to the fault man-
ager.
Requirements:
■
The control unit must be programmed as
fault man-
ager
(code "79:1" in the
"General"
group).
■
The LON subscriber number must be programmed in
all control units.
■
The LON subscriber list in the fault manager must be
up to date.
Service menu:
1. Press
OK
and
simultaneously for approx. 4 s.
2.
"Service functions"
3.
"Subscriber check"
4. Select subscriber (e.g. subscriber 10).
5. Start the subscriber check with
"OK"
.
■
Successfully tested subscribers are designated with
"OK"
.
■
Unsuccessfully tested subscribers are identified with
"Not OK"
.
Note
To perform another subscriber check:
Create a new subscriber list with
"Delete list?"
(sub-
scriber list is updated).
Note
During the subscriber check, the display of the relevant
subscriber shows the subscriber no. and
"Wink"
for
approx. 1 min.
Scanning and resetting the "Service" display
After the limits specified in coding addresses "21" and
"23" in the
"Boiler"
group have been reached, the red
fault indicator flashes and
"Service"
and "
¸
" appear
on the programming unit display.
Acknowledging and resetting service
Press
OK
to acknowledge a service message.
Commissioning, inspection, maintenance
Connecting the control unit to LON
(cont.)
5678 044 GB
Содержание D2RA
Страница 34: ...34 1 3 4 2 2x 5 5 Fig 24 Installation sequence Fitting the front panels 5678 044 GB Installation ...
Страница 113: ...113 Maintenance Checking the Vitotronic 200 H accessories cont 5678 044 GB Maintenance ...
Страница 126: ...126 0004 0002 0004 0002 0001 0001 0002 0004 0002 0003 Fig 79 Parts lists Sorption module 5678 044 GB Components ...
Страница 133: ...133 Parts lists Sorption module hydraulics cont 5678 044 GB Components ...
Страница 136: ...136 0001 0002 0003 0004 0005 Fig 83 Parts lists Miscellaneous 5678 044 GB Components ...
Страница 163: ...163 5678 044 GB ...