88
Gas boiler, type B and C, category I
2N
/I
2H
Type
B0KA
BPKA
Rated heating output range (details to EN 15502)
T
F
/T
R
= 50/30 °C
Natural gas
kW
3.2 (7.0
*1
) - 19.0
3.2 (7.0
*1
) - 25.0
T
F
/T
R
= 80/60 °C
Natural gas
kW
2.9 (6.3
*1
) - 17
2.9 (6.3
*1
) - 22.5
Rated heating output for DHW heating
Natural gas
kW
2.9 (6.3
*1
) - 25.4
2.9 (6.3
*1
) - 30
Rated heat input (Qn)
Natural gas
kW
3.0 (6.5
*1
) - 18.0
3.0 (6.5
*1
) - 23.6
Rated heat input for DHW heating (Qnw)
Natural gas
kW
3.0 (6.5
*1
) - 26.7
3.0 (6.5
*1
) - 31.5
Product ID
CE-0063DL3422
IP rating
to EN 60529
IP X4 to EN 60529
B1BA: IP X5 to EN 60529
NO
x
6
6
Gas supply pressure
Natural gas
mbar
kPa
20
2
20
2
Max. permiss. gas supply pressure
*2
Natural gas
mbar
kPa
25.0
2.5
25.0
2.5
Sound power level
(to EN ISO 15036-1)
At partial load
dB(A)
33
33
At rated heating output (DHW heating)
dB(A)
52
53
Power consumption
(in the delivered condition)
W
45
64
Rated voltage
V
230
Rated frequency
Hz
50
Appliance fuse protection
A
4
Backup fuse (power supply)
A
16
Communication module
(integral)
WiFi frequency band
MHz
2400 - 2483.5
Max. transmission power
dBm
20
Low power radio frequency band
MHz
2400 - 2483.5
Max. transmission power
dBm
10
Supply voltage
V
24
Power consumption
W
4
Electronic temperature limiter setting (TN)
°C
91
Electronic temperature cut-out setting
°C
110
Permissible ambient temperature
■
During operation
°C
+5 to +40
■
During storage and transport
°C
-5 to +60
*1
Appliances for multiple connection of type B0KA-[kW]-M
*2
If the gas supply pressure is higher than the maximum permissible value, install a separate gas pressure governor up-
stream of the system.
Specification
Gas condensing combi boiler
6173886
Service
Содержание B0KA
Страница 14: ...14 1 4 5 3 2 Fig 4 Installation sequence Removing the boiler from the packaging 6173886 Installation ...
Страница 28: ...28 1 2 Fig 20 Installation sequence Fitting the front panel 6173886 Installation ...
Страница 78: ...78 1 2 3 6 4 5 7 Fig 42 Troubleshooting Repairs cont 6173886 Diagnosis ...