52
6 "Minimum heating output"
Setting
Explanations
A limit can be set on the minimum heating output for
heating mode.
...
Delivered condition specified by settings specific to
the appliance
0 to 100
Adjustable from 0 to 100 %
7 "Maximum heating output"
Setting
Explanations
A limit can be set on the maximum heating output for
heating mode.
100
Heating output in the delivered condition 100 %
0 to 100
Adjustable from 0 to 100 %
9 "Maximum flow temperature limit, heating circuit 1"
Setting
Explanations
Maximum flow temperature limit for the heating circuit
Maximum limit in the delivered condition 82 °C
Setting range limited by heat generator-specific pa-
rameters
Energy saving functions (setting only via software tool)
2426.1 Weather-compensated heating circuit pump logic function (only for weather-compensated control
units).
Setting
Explanations
If the outside temperature is above the threshold val-
ue (selected set room temperature plus hysteresis
in K), the heating circuit pump is switched off.
If the outside temperature is above the threshold val-
ue (selected set room temperature plus hysteresis
in K), the heating circuit pump is switched off.
2426.2 Room temperature-dependent heating circuit pump logic (only for weather-compensated control
units with room temperature hook-up).
Setting
Explanations
Only activate this function for the heating
circuit with mixer or if there is only one di-
rect heating circuit in the system.
If the outside temperature is above the threshold val-
ue (selected set room temperature plus hysteresis
in K), the heating circuit pump is switched off.
If the outside temperature is above the threshold val-
ue (selected set room temperature plus hysteresis
in K), the heating circuit pump is switched off.
System configuration (parameters)
Parameters
(cont.)
6173886
Parameter
Содержание B0KA
Страница 14: ...14 1 4 5 3 2 Fig 4 Installation sequence Removing the boiler from the packaging 6173886 Installation ...
Страница 28: ...28 1 2 Fig 20 Installation sequence Fitting the front panel 6173886 Installation ...
Страница 78: ...78 1 2 3 6 4 5 7 Fig 42 Troubleshooting Repairs cont 6173886 Diagnosis ...