82
Pump/component
Parameter
Setting
Remote control (e.g.
Vitotrol 200A)
"Heating circuit 1"
Ó
"Remote control 2003"
or
"Heating circuit 2"
Ó
"Remote control 3003"
"1"
Note
Set code at the Vitotrol 200A
to assign heating circuits:
H1 for heating circuit 1
H2 for heating circuit 2
(see Vitotrol 200 A installa-
tion instructions)
Vitocom 100
"System definition"
Ó
"Vitocom 100 7017"
"1"
External extension H1
"System definition"
Ó
"External extension
7010"
"1"
Note
For parameters for external
hook-up, see the following
table.
External hook-up to external extension H1
External hook-up
Parameter
Setting
External demand
If necessary
"Internal
hydraulics"
Ó
"Flow temperature for
external demand 730C"
Set flow temperature for
external demand
External mixer OPEN
"System definition"
Ó
"Effect of external
demand on heat pump/
heating circuits 7014"
"0"
to
"7"
(Observe parameter
"Flow
temperature for external
demand 730C"
)
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5724 152 GB
Содержание AWS 104
Страница 5: ...5 Certificates Declaration of conformity 119 Keyword index 120 Index Index cont 5724 152 GB...
Страница 86: ...86 Placing the control panel in its service position 4x 1 2 3 Troubleshooting Repairs 5724 152 GB...
Страница 87: ...87 Opening programming unit 3 2 1 2x Troubleshooting Repairs cont 5724 152 GB Service...
Страница 88: ...88 Removing cover from programming unit if necessary 5 4 4x Troubleshooting Repairs cont 5724 152 GB...
Страница 89: ...89 Removing separating plate 1 2 Troubleshooting Repairs cont 5724 152 GB Service...
Страница 98: ...98 101 300 104 231 100 232 230 105 103 103 300 A Parts lists Parts list internal unit cont 5724 152 GB...
Страница 106: ...106 622 614 643 670 642 615 616 637 640 639 669 Parts lists Parts list external unit type AWS AWS AC cont 5724 152 GB...