66
For further information regarding the individual steps, see the page indicated
Commissioning steps
Inspection steps
Maintenance steps
Page
•
•
•
1. Opening the heat pump
.................................................. 68
•
2. Writing reports
................................................................ 68
•
3. Flushing the refrigerant lines and the internal unit
with nitrogen (the internal unit is filled with nitrogen;
operating pressure approx. 1 bar)
•
4. Tightness and pressure test with dry nitrogen at
43 bara/4.3 MPa
•
5. Evacuating the refrigerant lines and internal unit
....... 69
•
6. Filling the refrigerant lines and internal unit
................ 71
•
•
•
7. Checking the refrigerant circuit for leaks
..................... 73
•
8. Filling and venting on the secondary side
................... 73
•
•
•
9. Checking expansion vessel and heating circuit
pressure
........................................................................... 76
•
•
10. Checking electrical connections of the internal unit
for firm seating
•
•
•
11. Checking the condensate connection to the external
unit
................................................................................... 77
•
•
•
12. Checking the free running of the fan in the external
unit
................................................................................... 77
•
13. Cleaning the heat exchanger in the external unit
........ 77
•
14. Checking the thermal insulation on the swaged joints
•
•
15. Checking electrical connections of the external unit
for firm seating
•
•
•
16. Closing the heat pump; resetting the circuit breaker/
main fuse
•
17. Commissioning the system
........................................... 78
Commissioning, inspection, maintenance
Steps - commissioning, inspection and maintenance
5724 152 GB
Содержание AWS 104
Страница 5: ...5 Certificates Declaration of conformity 119 Keyword index 120 Index Index cont 5724 152 GB...
Страница 86: ...86 Placing the control panel in its service position 4x 1 2 3 Troubleshooting Repairs 5724 152 GB...
Страница 87: ...87 Opening programming unit 3 2 1 2x Troubleshooting Repairs cont 5724 152 GB Service...
Страница 88: ...88 Removing cover from programming unit if necessary 5 4 4x Troubleshooting Repairs cont 5724 152 GB...
Страница 89: ...89 Removing separating plate 1 2 Troubleshooting Repairs cont 5724 152 GB Service...
Страница 98: ...98 101 300 104 231 100 232 230 105 103 103 300 A Parts lists Parts list internal unit cont 5724 152 GB...
Страница 106: ...106 622 614 643 670 642 615 616 637 640 639 669 Parts lists Parts list external unit type AWS AWS AC cont 5724 152 GB...