108
Setting and test values
Set value
Commission-
ing
Testing the external heating circuit pumps
Circulation pump type
Circulation pump stage
Overflow valve setting
Primary circuit commissioning
Air inlet temperature
°C
Air outlet temperature
°C
Temperature differential ΔT:
Secondary circuit flow temperature =
35 °C at air inlet temperature
≤
15 °C
K
3 to 5
Secondary circuit flow temperature =
35 °C at air inlet temperature > 15 °C
K
2 to 4
Testing the mixer, heat pump and cylinder heating
Checked under the following conditions:
Room temperature
°C
Outside air temperature
°C
Temperature "
Cylinder temp. top
" con-
stant?
Yes (±1 K)
Secondary circuit flow temperature
°C
rising
from
to
Temperature differential ΔT
"
Flow temp. secondary
" / "
Return temp.
sec.
"
6 to 8 K
Control parameters report
For a description of parameters, see
separate service instructions, heat pump
control unit.
Commissioning/service reports
Hydraulic parameters report
5724 152 GB
Содержание AWS 104
Страница 5: ...5 Certificates Declaration of conformity 119 Keyword index 120 Index Index cont 5724 152 GB...
Страница 86: ...86 Placing the control panel in its service position 4x 1 2 3 Troubleshooting Repairs 5724 152 GB...
Страница 87: ...87 Opening programming unit 3 2 1 2x Troubleshooting Repairs cont 5724 152 GB Service...
Страница 88: ...88 Removing cover from programming unit if necessary 5 4 4x Troubleshooting Repairs cont 5724 152 GB...
Страница 89: ...89 Removing separating plate 1 2 Troubleshooting Repairs cont 5724 152 GB Service...
Страница 98: ...98 101 300 104 231 100 232 230 105 103 103 300 A Parts lists Parts list internal unit cont 5724 152 GB...
Страница 106: ...106 622 614 643 670 642 615 616 637 640 639 669 Parts lists Parts list external unit type AWS AWS AC cont 5724 152 GB...