At the air vent valve of the secondary
circuit
B
, connect the on-site hose
to prevent damage to electrical com-
ponents.
Open air vent valve
B
of the secon-
dary circuit.
9.
Move 3-way diverter valve
C
by its
handle into its centre position.
10.
Close air vent valve
B
of the sec-
ondary circuit.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5724 152 GB
Service