5.5 Configuration with DIP switches
A number of settings can be changed using DIP switches (see appendix A, position M).
This is done as follows:
Turn the Quattro on, preferably unloaded en without AC voltage on the inputs. The Quattro will then operate in inverter mode.
Step 1
: Setting the DIP switches for:
- the required current limitation of the AC inputs.
- limitation of the charging current.
- selection of stand-alone, parallel or 3-phase operation.
To store the settings after the required values have been set: press the 'Up' button for 2 seconds (
upper
button to the right of the DIP
switches, see appendix A, position K). You can now re-use the DIP switches to apply the remaining settings (step 2).
Step 2
: other settings
To store the settings after the required values have been set: press the 'Down' button for 2 seconds (
lower
button to the right of the
DIP switches). You can now leave the DIP switches in the selected positions, so that the ’other settings’ can always be recovered.
Remarks:
- The DIP switch functions are described in 'top to bottom' order. Since the uppermost DIP switch has the highest number (8),
descriptions start with the switch numbered 8.
- In parallel mode or 3-phase mode, not all devices require all settings to be made (see section 5.5.1.4).
For parallel or 3-phase mode, read the whole setting procedure and make a note of the required DIP switch settings before actually
implementing them.
5.5.1 Step 1
5.5.1.2 Current limitation AC inputs (default: AC-in-1: 30A, AC-in-2: 16A)
If the current demand (Quattro load + battery charger) threatens to exceed the set current, the Quattro will first reduce its charging
current (PowerControl), and subsequently supply additional power from the battery (PowerAssist), if needed.
The AC-in-1 current limit (the generator) can be set to eight different values by means of DIP switches.
The AC-in-2 current limit can be set to two different values by means of DIP switches. With a Phoenix Multi Control Panel, a variable
current limit can be set for the AC-in-2 input.
Remark
: Using a Duo Control Panel is pointless if the internal transfer switch of the Quattro is used, because only the AC-in-2 input
current can be set with the panel.
Procedure
AC-in-1 can be set using DIP switches ds8, ds7 and ds6 (default setting: 30A).
Procedure: set the DIP switches to the required value:
ds8 ds7 ds6
off off off = 6A (1.4kVA at 230V)
off off on = 10A (2.2kVA at 230V)
off on off = 12A (2.8kVA at 230V)
off on on = 16A (3.7kVA at 230V)
on off off = 20A (4.6kVA at 230V)
on off on = 23A (5.3kVA at 230V)
on on off = 26A (6.0kVA at 230V)
on on on = 30A (6.9kVA at 230V)
Remark:
Manufacturer-specified continuous power ratings for small generators are sometimes inclined to be rather
optimistic. In that case, the current limit should be set to a much lower value than would otherwise be required
on the basis of manufacturer-specified data.
AC-in-2 can be set in two steps using DIP switch ds5 (default setting: 16A).
Procedure: set ds5 to the required value:
ds5
off = 16A
on = 30A