23
5.5.2 Step 2: Other settings
The remaining settings are not relevant for slaves.
Some of the remaining settings are not relevant for followers (
L2
,
L3)
. These settings are imposed on the whole system by the leader
L1
. If a setting is irrelevant for
L2
,
L3
devices, this is mentioned explicitly.
ds8-ds7: Setting charging voltages (
not relevant for L2,
L3
)
ds8-ds7
Absorption voltage
Float voltage
Storage voltage
Suitable for
off off
14.1 / 28.2 / 56.4
13.8 / 27.6 / 55.2
13.2 / 26.4 / 52.8
Gel Victron Long Life (OPzV)
Gel Exide A600 (OPzV), Gel MK battery
off on
14.4 / 28.8 / 57.6
13.8 / 27.6 / 55.2
13.2 / 26.4 / 52.8
Gel Victron Deep Discharge, Gel Exide A200
AGM Victron Deep Discharge
Stationary tubular plate batteries (OPzS)
on off
14.7 / 29.4 / 58.8
13.8 / 27.6 / 55.2
13.2 / 26.4 / 52.8
AGM Victron Deep Discharge
Tubular plate traction batteries in semi-float mode
AGM spiral cell
on on
15.0 / 30.0 / 60.0
13.8 / 27.6 / 55.2
13.2 / 26.4 / 52.8
Tubular plate traction batteries in cyclic mode
ds6: absorption time 8 or 4 hours (
not relevant for L2, L3
)
on = 8 hours
off = 4 hours
ds5: adaptive charging characteristic (
not relevant for L2, L3
)
on = active
off = inactive (fixed absorption time)
ds4: dynamic current limiter
on = active
off = inactive
ds3: UPS function
on = active
off = inactive
ds2: converter voltage
on = 230V / 120V
off = 240V / 115V
ds1: converter frequency (
not relevant for L2, L3
)
on = 50Hz
off = 60Hz
(the wide input frequency range (45-55Hz) is 'on' by default)
Step 2: Exemplary settings for stand-alone mode
Example 1 is the factory setting (since factory settings are entered by computer, all DIP switches of a new product are set to ‘off’).
DS-8 Charging voltage
off
DS-7 Charging voltage
on
DS-6 Absorption time
on
DS-5 Adaptive charging
on
DS-4 Dyn. current limit
off
DS-3 UPS function:
on
DS-2 Voltage
on
DS-1 Frequency
on
DS-8
off
DS-7
off
DS-6
on
DS-5
on
DS-4
off
DS-3
off
DS-2
on
DS-1
on
DS-8
on
DS-7
off
DS-6
on
DS-5
on
DS-4
on
DS-3
off
DS-2
off
DS-1
on
DS-8
on
DS-7
on
DS-6
off
DS-5
off
DS-4
off
DS-3
on
DS-2
off
DS-1
off
Step 2
Example 1 (factory setting):
8, 7 GEL 14,4V
6 Absorption time: 8 hours
5 Adaptive charging: on
4 Dynamic current limit: off
3 UPS function: on
2 Voltage: 230V
1 Frequency: 50Hz
Step 2
Example 2:
8, 7 OPzV 14,1V
6 Absorption time: 8
hours
5 Adaptive charging: on
4 Dynamic current limit:
off
3 UPS function: off
2 Voltage: 230V
1 Frequency: 50Hz
Step 2
Example 3:
8, 7 AGM 14,7V
6 Absorption time: 8 hours
5 Adaptive charging: on
4 Dynamic current limit: on
3 UPS function: off
2 Voltage: 240V
1 Frequency: 50Hz
Step 2
Example 4:
8, 7 Tube-plate 15V
6 Absorption time: 4 hours
5 Fixed absorption time
4 Dynamic current limit: off
3 UPS function: on
2 Voltage: 240V
1 Frequency: 60Hz
To store the settings after the required values have been set: press the 'Down' button for 2 seconds (
lower
button to the right of the
DIP switches).
The temperature and low-battery LEDs will flash to indicate acceptance of the settings.
You can then leave the DIP switches in the selected positions, so that the ’other settings’ can always be recovered.