7.3.2 VE.Bus error codes
A VE.Bus system can display various error codes. These codes are displayed with the "inverter on", "bulk", "absorption" and "float"
LEDs.
To interpret a VE.Bus error code correctly, the following procedure should be followed:
1.
Is the "inverter on" LED flashing? If not, then there is
no
VE.Bus error code.
2.
If one or more of the LEDs "bulk", "absorption" or "float" flashes, then this flash must be in phase opposition to the "inverter
on" LED, i.e. the flashing LEDs are off if the "inverter on" LED is on, and vice versa. If this is not the case, then there is
no
VE.Bus error code.
3.
Check the "bulk" LED, and determine which of the three tables below should be used.
4.
Select the correct column and row (depending on the "absorption" and "float" LEDs), and determine the error code.
5.
Determine the meaning of the code in the table below.
Bulk LED off
Bulk LED flashes
Bulk LED on
Absorption LED
Absorption LED
Absorption LED
off
flashing
on
off
flashing
on
off
flashing
on
off
0
3
6
off
9
12
15
off
18
21
24
flashing
1
4
7
flashing
10
13
16
flashing
19
22
25
F
lo
a
t
L
E
D
on
2
5
8
F
lo
a
t
L
E
D
on
11
14
17
F
lo
a
t
L
E
D
on
20
23
26
Code
Meaning:
Cause/solution:
1
Device is switched off because one of the other phases
in the system has switched off.
Check the failing phase.
The system is not properly configured. Reconfigure the system.
3
Not all, or more than, the expected devices were found
in the system.
Communication cable error. Check the cables and switch all
equipment off, and then on again.
4
No other device whatsoever detected.
Check the communication cables.
5
Overvoltage on AC-out.
Check the AC cables.
10
System time synchronisation problem occurred.
Should not occur in correctly installed equipment. Check the
communication cables.
14
Device cannot transmit data.
Check the communication cables (there may be a short circuit).
16
System is switched off because it is a so-called
extended system and a ‘dongle’ is not connected.
Connect dongle.
17
One of the devices has assumed ‘master’ status
because the original master failed.
Check the failing unit. Check the communication cables.
18
Overvoltage has occurred.
Check AC cables.
22
This device cannot function as ‘slave’.
This device is an obsolete and unsuitable model. It should be
replaced.
24
Switch-over system protection initiated.
Should not occur in correctly installed equipment. Switch all
equipment off, and then on again. If the problem recurs, check the
installation.
25
Firmware incompatibility. The firmware of one the
connected devices is not sufficiently up to date to
operate in conjunction with this device.
1) Switch all equipment off.
2) Switch the device returning this error message on.
3) Switch on all other devices one by one until the error message
reoccurs.
4) Update the firmware in the last device that was switched on.
26
Internal error.
Should not occur. Switch all equipment off, and then on again.
Contact Victron Energy if the problem persists.