background image

 

17 

 

5.3 Configuration by computer 

All settings can be changed by means of a computer or with a VE.Net panel (except for the multi-functional relay and the VirtualSwitch 
when using VE.Net). 
The most common settings (including parallel and 3-phase operation) can be changed by means of DIP switches (see Section 5.4). 
 
For changing settings with the computer, the following is required: 

VEConfigureII software. You can download the VEConfigureII software free of charge at 

www.victronenergy.com

 . 

A RJ45 UTP cable and the 

MK2.2b

 RS485-to-RS232 interface. If your computer has no RS232 connection, but does have 

USB, you will also need a 

RS232-to-USB interface cable

. Both are available from Victron Energy. 

 

5.3.1 VE.Bus Quick Configure Setup

 

VE.Bus Quick Configure Setup

 is a software program with which one Quattro unit or systems with a maximum of three Quattro units 

(parallel or three phase operation) can be configured in a simple manner. VEConfigureII forms part of this program. 
You can download the software free of charge at 

www.victronenergy.com

 . 

For connection to your computer, a RJ45 UTP cable and the 

MK2.2b

 RS485-to-RS232 interface is required. 

If your computer does not have a RS232 connection but is equipped with USB, you will also need a 

RS232-to-USB interface cable

Both are available from Victron Energy. 
 

5.3.2 VE.Bus System Configurator and dongle 

For configuring advanced applications and/or systems with four or more Quattro units, 

VE.Bus System Configurator

 software must 

be used. You can download the software at 

www.victronenergy.com

 . VEConfigureII forms part of this program. 

You can configure the system without a dongle, and use it for 15 minutes (as a demonstration facility). For permanent use, a dongle – 
available at additional charge – is required. 
For connection to your computer, a RJ45 UTP cable and the 

MK2.2b

 RS485-to-RS232 interface is required. 

If your computer does not have a RS232 connection but is equipped with USB, you will also need a 

RS232-to-USB interface cable

Both are available from Victron Energy. 

 

5.4 Implementing settings with a VE.Net panel 

To this end, a VE.Net panel and the VE.Net to VE.Bus converter is required. 
With VE.Net you can set all parameters, with the exception of the multi-functional relay and the VIrtualSwitch. 

Содержание Quattro 12/5000/200

Страница 1: ...TION MANUAL Quattro 12 5000 200 Quattro 24 5000 120 Quattro 48 5000 70 Remark DIP switch functionality has changed with respect to the MultiPlus product Parallel and 3 phase systems can be now configured with DIP switches ...

Страница 2: ... terminals must be provided with uninterruptable grounding for safety purposes An additional grounding point is located on the outside of the product If it can be assumed that the grounding protection is damaged the product should be taken out of operation and prevented from accidentally being put into operation again contact qualified maintenance personnel Ensure that the connection cables are pr...

Страница 3: ...tended use of your generating set and shore current the Quattro co supply feature The Quattro operates in parallel with the generating set or the shore connection A current shortfall is automatically compensated the Quattro draws extra power from the battery and helps along A current surplus is used to recharge the battery This unique feature offers a definitive solution for the shore current prob...

Страница 4: ...han 24 hours The voltage is then lowered to 2 2 V cell 13 2 V for a 12 V battery Gas formation in the battery will then be drastically reduced and corrosion of the positive plates is limited as much as possible Once a week the voltage is increased to absorption level to recharge the battery this prevents stratification of the electrolyte and sulphate formation Two DC outputs for charging two batte...

Страница 5: ...ge level In Forced Absorption mode the Phoenix Multi will charge at the normal absorption voltage level during the set maximum absorption time The absorption LED lights 3 3 3 Activating equalisation or forced absorption The Quattro can be put into both these states from the remote panel as well as with the front panel switch provided that all switches front remote and panel are set to on and no sw...

Страница 6: ...rload LED flashes charger inverter mains on inverter on on bulk overload off absorption low battery float charger only temperature The inverter is switched off due to overload or short circuit charger inverter mains on inverter on on bulk overload off absorption low battery float charger only temperature The battery is almost empty charger inverter mains on inverter on on bulk overload off absorpt...

Страница 7: ...attery float charger only temperature charger inverter mains on inverter on on bulk overload off absorption low battery float charger only temperature The inverter is switched off due to excessively high internal temperature ...

Страница 8: ...t charger only temperature The AC voltage on AC in 1 or AC in 2 is switched through and the charger operates in bulk phase charger inverter mains on inverter on on bulk overload off absorption low battery float charger only temperature The AC voltage on AC in 1 or AC in 2 is switched through and the charger operates but the set absorption voltage has not yet been reached battery protection mode ch...

Страница 9: ...r inverter mains on inverter on on bulk overload off absorption low battery float charger only temperature The AC voltage on AC in 1 or AC in 2 is switched through and the charger operates in equalisation mode ...

Страница 10: ...through The AC input current is equal to the load current The charger is down controlled to 0A Set to supply additional current charger inverter mains on inverter on on bulk overload off absorption low battery float charger only temperature The AC voltage on AC in 1 or AC in 2 is switched through but the load demands more current than the mains can supply The inverter is now switched on to supply ...

Страница 11: ... For optimal cooling vertical fitting is preferred The inner part of the device should remain well accessible after installation The distance between the Quattro and the battery should be as short as possible to reduce voltage loss across the battery leads to a minimum Install the product in a heatproof environment Ensure therefore that there are no chemicals plastic parts curtains or other textil...

Страница 12: ...ions in this regard The Quattro is provided with a ground relay see appendix that automatically connects the N output to the casing if no external AC supply is available If an external AC supply is provided the ground relay will open before the input safety relay closes relay H in appendix B This ensures the correct operation of an earth leakage circuit breaker that is connected to the output In a...

Страница 13: ... compensating possible cable losses during charging two sense wires can be connected with which the voltage direct on the battery or on the positive and negative distribution points can be measured Use at least wire with a cross section of 0 75mm2 During battery charging the Quattro will compensate the voltage drop over the DC cables to a maximum of 1 Volt i e 1V over the positive connection and 1...

Страница 14: ...each other but allow at least 10 cm for ventilation purposes under above and beside the units UTP cables must be connected directly from one unit to the other and to the remote panel Connection splitter boxes are not permitted A battery temperature sensor need only be connected to one unit in the system If the temperature of several batteries is to be measured you can also connect the sensors of o...

Страница 15: ...8 8 57 6 V Absorption time up to 8 hours depending on bulk time Float voltage 13 8 27 6 55 2 V Storage voltage 13 2V not adjustable Repeated absorption time 1 hour Absorption repeat interval 7 days Bulk protection on Generator AC in 1 shore current AC in 2 30A 16A current limit for PowerControl and PowerAssist functions UPS feature on Dynamic current limiter off WeakAC off BoostFactor 2 Multi func...

Страница 16: ...Four charging voltages can be set with DIP switches Absorption time This depends on the bulk time adaptive charging characteristic so that the battery is optimally charged If the fixed charging characteristic is selected the absorption time is fixed For most batteries a maximum absorption time of eight hours is suitable If an extra high absorption voltage is selected for rapid charging only possib...

Страница 17: ...lay is set as an alarm relay i e the relay will de energise in the event of an alarm or a pre alarm inverter almost too hot ripple on the input almost too high battery voltage almost too low Not adjustable with DIP switches VirtualSwitch The VirtualSwitch is a software function in the Quattro microprocessor The inputs of this function are parameters that can be selected with VEConfigure e g certai...

Страница 18: ...ronenergy com For connection to your computer a RJ45 UTP cable and the MK2 2b RS485 to RS232 interface is required If your computer does not have a RS232 connection but is equipped with USB you will also need a RS232 to USB interface cable Both are available from Victron Energy 5 3 2 VE Bus System Configurator and dongle For configuring advanced applications and or systems with four or more Quattr...

Страница 19: ...lly implementing them 5 5 1 Step 1 5 5 1 2 Current limitation AC inputs default AC in 1 30A AC in 2 16A If the current demand Quattro load battery charger threatens to exceed the set current the Quattro will first reduce its charging current PowerControl and subsequently supply additional power from the battery PowerAssist if needed The AC in 1 current limit the generator can be set to eight diffe...

Страница 20: ...ee Section 7 since they have been integrated into a system and still are configured as stand alone This error message can safely be ignored Storing settings by pressing the Up button step 1 and later on the Down button step 2 for 2 seconds should be done on one device only This device is the master in a parallel system or the leader L1 in a 3 phase system In a parallel system the step 1 settings o...

Страница 21: ...ches to apply the remaining settings step 2 DS 8 AC in 1 on DS 7 AC in 1 on DS 6 AC in 1 on DS 5 AC in 2 off DS 4 Charging current on DS 3 Charging current off DS 2 Stand alone mode off DS 1 Stand alone mode off DS 8 on DS 7 on DS 6 on DS 5 off DS 4 on DS 3 on DS 2 off DS 1 off DS 8 off DS 7 on DS 6 on DS 5 off DS 4 on DS 3 on DS 2 off DS 1 off DS 8 on DS 7 on DS 6 off DS 5 on DS 4 off DS 3 on DS ...

Страница 22: ...of the DIP switches see appendix A position K The overload and low battery LEDs will flash to indicate acceptance of the settings We recommend making a note of the settings and filing this information in a safe place You can now re use the DIP switches to apply the remaining settings step 2 Master Slave 1 Slave 2 DS 8 AC in 1 3 x 20 60A on DS 7 AC in 1 3 x 20 60A off DS 6 AC in 1 3 x 20 60A off DS...

Страница 23: ...lash to indicate acceptance of the settings We recommend making a note of the settings and filing this information in a safe place You can now re use the DIP switches to apply the remaining settings step 2 Leader L1 Follower L2 Follower L3 DS 8 AC in 1 16A off DS 7 AC in 1 16A on DS 6 AC in 1 16A on DS 5 AC in 2 Not relevant 16A panel DS 4 Charging current 3 x 120 360A on DS 3 Charging current 3 x...

Страница 24: ...y default Step 2 Exemplary settings for stand alone mode Example 1 is the factory setting since factory settings are entered by computer all DIP switches of a new product are set to off DS 8 Charging voltage off DS 7 Charging voltage on DS 6 Absorption time on DS 5 Adaptive charging on DS 4 Dyn current limit off DS 3 UPS function on DS 2 Voltage on DS 1 Frequency on DS 8 off DS 7 off DS 6 on DS 5 ...

Страница 25: ...art up as soon as all devices have been turned on 6 Maintenance The Quattro does not require specific maintenance It will suffice to check all connections once a year Avoid moisture and oil soot vapours and keep the device clean Leader L1 Follower L2 Follower L3 DS 8 Charging voltage GEL 14 4V off DS 7 Charging voltage GEL 14 4V on DS 6 Absorption time 8 hours on DS 5 Adaptive charging on on DS 4 ...

Страница 26: ... connections Check whether battery capacity is sufficiently high and increase this if necessary Low battery and overload LEDs light The inverter is switched off due to an excessively high ripple voltage on the input Install batteries with a larger capacity Fit shorter and or thicker battery cables and reset the inverter switch off and then on again One alarm LED lights and the second flashes The i...

Страница 27: ...n extremely unlikely value The sensor is probably defective or has been incorrectly connected The device will remain in normal operation NOTE If the inverter on LED flashes in phase opposition this a VE Bus error code see further on Mains on flashes and there is no output voltage The device is in charger only operation and mains supply is present The device rejects the mains supply or is still syn...

Страница 28: ...e expected devices were found in the system Communication cable error Check the cables and switch all equipment off and then on again 4 No other device whatsoever detected Check the communication cables 5 Overvoltage on AC out Check the AC cables 10 System time synchronisation problem occurred Should not occur in correctly installed equipment Check the communication cables 14 Device cannot transmi...

Страница 29: ...battery A 4 200 120 70 Charge current starter battery A 4 Battery temperature sensor ja GENERAL Multi purpose relay 5 Yes Yes Yes Protection 2 a g Common Characteristics Operating temp 20 to 50 C fan assisted cooling Humidity non condensing max 95 ENCLOSURE Common Characteristics Material Colour aluminium blue RAL 5012 Protection category IP 21 Battery connection Four M8 bolts 2 plus and 2 minus c...

Страница 30: ...29 APPENDIX A Connection overview ...

Страница 31: ...0A thermal circuit breaker in series with AC in 2 bottom cabinet right A Wisselspanning ingang generator AC in 1 Van links naar rechts L fase N nul PE aarde B 2x RJ45 connector voor afstandbedieningspaneel en of parallel and 3 fase bedrijf C Wisselspanning uitgang AC out 1 Van links naar rechts L fase N nul PE aarde D Wisselspanning uitgang AC out 2 Van links naar rechts L fase N nul Max stroom 16...

Страница 32: ...31 APPENDIX B Block diagram ...

Страница 33: ...32 APPENDIX C Parallel connection ...

Страница 34: ...33 APPENDIX D Three phase connection ...

Страница 35: ...ry is raised gradually until the set Absorption voltage is reached The Battery Safe Mode is part of the calculated absorption time Absorption The absorption period is dependent on the bulk period The maximum absorption time is the set Maximum Absorption time Float Float voltage is applied to keep the battery fully charged Storage After one day of float charge the output voltage is reduced to stora...

Страница 36: ...0 25 30 35 40 45 50 55 60 Battery temperature Volts 20 21 22 23 24 25 26 27 28 29 30 Volts Default output voltages for Float and Absorption are at 25 C Reduced Float voltage follows Float voltage and Raised Absorption voltage follows Absorption voltage In adjust mode temperature compensation does not apply ...

Страница 37: ...36 APPENDIX G Dimensions ...

Страница 38: ...Distributor Victron Energy B V The Netherlands Phone 31 0 36 535 97 00 Fax 31 0 36 535 97 40 E mail sales victronenergy com Web site http www victronenergy com Article number ISMQUATTRO5000_GB Version 01 Date 20 09 2007 ...