Figure 3. Connection sequence when connecting two Lynx modules
Lynx module
M8 bolt
M8 Spring washer
M8 Washer
Lynx module
Correct placement of the M8 washer, spring washer and nut.
6.1.3. Addressing Lynx Distributor
These instructions only apply if the system contains a Lynx Smart BMS together with multiple Lynx Distributors and the serial
number of the Lynx Distributors is HQ1909 or above.
· Name the Lynx Distributors from left to right: A, B, C and D. Do this so that the fuse alarms correspond with the Lynx
Distributor names.
Figure 4. Example of Lynx Distributor configuration and labelling
A
B
C
D
Set the 2-way DIP switch in each Lynx Distributor to correspond with its name. Up to 4 Lynx Distributors can be programmed this
way. See below table how to set the DIP switches for each unit. By default, both DIP switches are set to off (A).
Figure 5. Location of the Lynx Distributor 2 way DIP switch
2 way DIP switch
Table 2. Lynx Distributor DIP switch programming table
Distributor name
Switch 1
Switch 2
Configuration
A
Off
Off
B
On
Off
C
Off
On
D
On
Off
Lynx Distributor
Page 13
Installation