1.3 Power
Power the device using the Power in V+ connector. It accepts 8 to 70 V DC. The device will not power
itself from any of the network connections. Be sure to use a 1A slow blow fuse.
Powering in systems with VE.Bus BMS
When the CCGX is used in an installation with a VE.Bus BMS, connect the Power in V+ on the CCGX to
the terminal labelled 'Load disconnect' on the VE.Bus BMS. Connect both negative leads to the
negative stub of a common Battery.
A Cautionary word about Powering from the AC-out terminal of a VE.Bus Inverter, Multi or
Quattro:
If you power the CCGX from an AC adaptor connected to the AC-out port of any VE.Bus product
(Inverter, Multi or Quattro), then a deadlock will occur after the VE.Bus products are powered-down