I-VICFLEX.AB1/AB2/AB10

INSTALLATION INSTRUCTIONS

Victaulic

®

 VicFlex

 Flexible Hose with Fittings for Fire Protection Service 

Styles AB1, AB2, and AB10 Brackets

I-VICFLEX.AB1/AB2/AB10_1

REV_R

 WARNING

•  Read and understand all instructions before attempting to install any Victaulic products.
•  Always verify that the piping system has been completely depressurized and drained immediately prior 

to installation, removal, adjustment, or maintenance of any Victaulic products.

•  Confirm that any equipment, branch lines, or sections of piping that may have been isolated for/

during testing or due to valve closures/positioning are identified, depressurized, and drained 
immediately prior to installation, removal, adjustment, or maintenance of any Victaulic products.

•  Wear safety glasses, hardhat, and foot protection.
Failure to follow these instructions could result in death or serious  personal injury and property damage.

     

•  This Victaulic

®

 VicFlex

 product shall be used only in fire protection systems that are designed and installed in accordance with current, 

applicable National Fire Protection Association (NFPA 13, 13D, 13R, etc.) standards, or equivalent standards, and in accordance with 
applicable building and fire codes. These standards and codes contain important information regarding protection of systems from freezing 
temperatures, corrosion, mechanical damage, etc.

•  These installation instructions are intended for an experienced, trained installer. The installer shall understand the use of this product and 

why it was specified for the particular application.

•  The installer shall understand common industry safety standards and potential consequences of improper product installation.
•  It is the system designer’s responsibility to verify suitability of stainless steel flexible hose for use with the intended fluid media within the 

piping system and external environment.

•  The material specifier shall evaluate the effect of chemical composition, pH level, operating temperature, chloride level, oxygen level, and 

flow rate on stainless steel components to confirm system life will be acceptable for the intended service.

Failure to follow installation requirements and local and national codes and standards could compromise system integrity or cause system 
failure, resulting in death or serious personal injury and property damage.

Flexible Hose Listing and Approval Information

Flexible Hose

G412024

104l

AH1

With AB1, AB2, AB10

With AB1, AB2, AB10

With AB1, AB2, AB10

With AB1, AB2, AB10

With AB1, AB2, AB10

AH1-CC

With AB1, AB2, AB10

With AB1, AB2, AB10

With AB1, AB2, AB10

With AB1, AB2, AB10

AH2

With AB1, AB2, AB10

With AB1, AB2, AB10

With AB1, AB2, AB10

With AB1, AB2, AB10

With AB1, AB2, AB10

AH2-CC

With AB1, AB2, AB10

With AB1, AB2, AB10

With AB1, AB2, AB10

With AB1, AB2, AB10

AH2-300

With AB2

With AB1, AB2, AB10

AH2-CC-300

With AB2

With AB1, AB2, AB10

AH2-638

With AB1, AB2, AB10

AH3*

With AB2

With AB2

With AB1, AB2, AB10

AH4*

With AB1, AB2, AB10

With AB1, AB2, AB10

With AB1, AB2, AB10

* SERIES AH3 AND AH4 – REGIONAL AVAILABILITY ONLY

NOTE:

 Flexible hoses are available in lengths from 31 - 72 inches/787 - 1829 mm with either 1/2-inch/DN15 or 3/4-inch/DN20 NPT or BSPT threaded 

outlets.

Содержание VicFlex AB2

Страница 1: ...he use of this product and why it was specified for the particular application The installer shall understand common industry safety standards and potential consequences of improper product installati...

Страница 2: ...sentative is responsible for referencing applicable standards to determine if additional sprinklers or other system adjustments are required The building owner or their representative is responsible f...

Страница 3: ...cket Button Head Cap Screw 7 Hex Socket Button Head Cap Screw Hex Socket Button Head Cap Screw Reference publication 10 85 for listing information Square bar length is in reference to nominal ceiling...

Страница 4: ...ted in the NOTICE below are met a thin coat of a compatible lubricant shall be applied only to the gasket sealing lips to help prevent pinching rolling or tearing during installation DO NOT use excess...

Страница 5: ...Metric nut deep well socket tighten the nut until metal to metal contact occurs at the bolt pads Verify that the oval neck of the bolt seats properly in the bolt hole DO NOT continue to tighten the n...

Страница 6: ...CC AH2 CC or AH2 CC 300 Flexible Hose NO 101 NO 102 5 Insert the inlet end of the Series AH1 CC AH2 CC or AH2 CC 300 Flexible Hose into the No 101 90 Elbow or No 102 Straight Tee Verify that the gaske...

Страница 7: ...thread sealant tape on the threads of the adapter nipple The seal inside the nut of the flexible hose provides the leak proof connection Tighten the connection nut to a torque of 40ft lbs 54N m approx...

Страница 8: ...TM C636 standards Verify that the ends of the Style AB1 AB2 or AB10 Bracket engage the rails Side Facing the Opening of the Center Gate Assembly 1a For center of tile installations align the end brack...

Страница 9: ...nch lbs 6 N m approximately hand tight plus 1 2 to 3 4 of a turn NOTE Verify that the washer is seated under the head of the wing nut 2c FOR STYLE AB2 BRACKETS ONLY Close the gate around the sprinkler...

Страница 10: ...re bar 2 Attach the end brackets of the Style AB2 Bracket to the T bar rails of the CD Profile 60 mm Channel Ceiling System Verify that the ends of the Style AB2 Bracket engage the rails 3 To secure t...

Страница 11: ...TALLATION FOR ASTM C645 METAL JOISTS STUDS INSTALLED IN ACCORDANCE WITH ASTM C754 STANDARDS FM ONLY FOR AB1 AND FM UL FOR AB2 1 Install the flexible hose into the sprinkler piping and the sprinkler re...

Страница 12: ...e of 36 inch lbs 4 N m approximately 1 2 to 3 4 of a turn past hand tight 7 Perform steps 2 2c on pages 8 9 to complete the installation ALTERNATIVE 1 METAL JOIST STUD INSTALLATION FM ONLY FOR AB1 AND...

Страница 13: ...e of 36 inch lbs 4 N m approximately 1 2 to 3 4 of a turn past hand tight 7 Perform steps 2 2c on pages 8 9 to complete the installation ALTERNATIVE 2 METAL JOIST STUD INSTALLATION FM ONLY FOR AB1 AND...

Страница 14: ...be removed The sprinkler piping s outside diameter OD groove dimensions and maximum allowable flare diameter shall be within the tolerances published in current Victaulic IGS specifications publicatio...

Страница 15: ...sponsibility to verify suitability of stainless steel flexible hose for use with the intended fluid media within the piping system and external environment The material specifier shall evaluate the ef...

Страница 16: ...end of a Series AH1 CC Flexible Hose the friction loss data shown above shall be added to the No 101 or No 102 friction loss data published in Victaulic publication 10 54 SERIES AH2 AND AH2 CC FLEXIB...

Страница 17: ...imum Number of 90 Bends AH2 300 31 AH2 CC 300 31 31 790 1 2 17 0 3 DN15 5 2 3 4 16 0 DN20 4 9 AH2 300 36 AH2 CC 300 36 36 915 1 2 25 0 4 DN15 7 6 3 4 22 0 DN20 6 7 AH2 300 48 AH2 CC 300 48 48 1220 1 2...

Страница 18: ...REGIONAL AVAILABILITY ONLY Model Length of Flexible Hose inches mm Outlet Size inches Metric Equivalent Length of 1 inch DN25 Schedule 40 Pipe feet meters Maximum Number of 90 Bends AH4 31 31 790 1 2...

Страница 19: ...nd AB10 Brackets AMF Armstrong Chicago Metallic Dipling Durlum Geipel Gema Armstrong Hilti Knauf Lafarge Lindner Odenwald Richter Rigips Rockfon Pagos Suckow Fischer USG Donn Other manufacturers ceili...

Страница 20: ...9 9 75 3 AH1 72 1830 72 14 26 25 98 46 8 85 2 178 mm 7 inch minimum bend radius Friction loss data is in accordance with GB5135 16 Corresponding flow rate is 113 55 liters per minute 30 gallons per mi...