23
14.
Open the water supply’s main control valve fully.
15.
Confirm that all valves are in their normal operating
positions (refer to table below).
16.
Notify the authority having jurisdiction, remote sta-
tion alarm monitors, and those in the affected area that
the valve is back in service.
17.
Provide test results to the authority having jurisdic-
tion, if required.
TRIP TESTS
Partial Trip Test
Partial trip tests are required to confirm proper valve oper-
ation; however, this test does not confirm full system
operation. Victaulic recommends that the partial trip test
be performed annually.
NOTE:
The authority having juris-
diction in your area may require that you perform this
partial trip test on a more frequent basis. Verify these
requirements by contacting the authority having jurisdic-
tion in the affected area.
1.
Notify the authority having jurisdiction, remote station
alarm monitors, and those in the affected area that the
partial trip test will be performed.
2.
Record the water supply pressure and the system air
pressure.
3.
Open the water supply main drain valve fully to flush
the water supply of any contaminants.
4.
Close the water supply main drain valve.
Valve
Normal Operating
Position
Piston Charge Line Ball Valve
Open
Alarm Line Ball Valve
Open
Alarm Test Ball Valve
Closed
Alarm Drain Ball Valve
Closed
Water Supply's
Main Control
Valve
Water Supply
Main Drain
Valve
Water Supply
Main Drain
Valve