19
4.
Close the alarm line ball valve.
5.
Open the alarm test ball valve. Confirm that mechanical
and electrical alarms provided are activated and that
remote monitoring stations, if provided, receive an alarm
signal.
6.
Close the alarm test ball valve after proper operation of
all alarms is verified.
7.
Open the alarm drain ball valve, as shown above.
8.
Verify that all alarms stopped sounding, that the alarm
line drained properly, and that remote station alarms reset
properly.
9.
Confirm that the alarm test ball valve is closed.
10.
Close the alarm drain ball valve.
Alarm Line
Ball Valve
Alarm Test
Ball Valve
Alarm Test
Ball Valve
Alarm Drain
Ball Valve
Alarm Test
Ball Valve
Alarm Drain
Ball Valve