PIR Ready VTR7300 Series 

Terminal Equipment Controllers 

For Commercial and Lodging HVAC Fan Coil Applications

 

(Issue Date: March 29, 2010 – 028-0298_R0) 

Product overview 

 

 

 

The VTR73XX Series Fan Coil Terminal Equipment Controller used in conjunction with 
the VC3000 Series Line Voltage Switching Relay Packs is specifically designed for fan 
coil control applications. They can be used both for new or retrofit applications. In 
retrofit applications, they can re-use the existing wires between the old line voltage 
switching thermostat and the fan coil thus saving on the installation of any new wires. 
Stand-alone and network operation are available. 
 
The VTR73XX Series Fan Coil Terminal Equipment Controller features a backlit LCD 
display with dedicated function menu buttons for simple operation. Accurate 
temperature control is achieved due to the product’s PI proportional control algorithm, 
which virtually eliminates temperature offset associated with traditional, differential-
based Terminal Equipment Controllers. All models feature configurable System and 
Fan button functions to meet all possible applications The VTR73XX Terminal 
Equipment Controllers are powered and communicate with the associated VC3000 Series Transformer Relay Pack(s) using 
only 3 wires. 
 
2 types of interfaces for the user can be ordered. The VC73x5 models are typically used for hotel and lodging applications 
where the middle button of the interface is for the user to select the local displayed scale in ºF or ºC. The VC73x0 models are 
typically used for commercial and institution applications where the middle button of the interface is defined for the local 
unoccupied override function. 
 
The VTR73XX Terminal Equipment Controllers are also compatible with the new Viconics PIR cover accessories. Terminal 
Equipment Controllers equipped with a PIR cover provide advanced active occupancy logic, which will automatically switch 
occupancy levels from Occupied to Stand-By and Unoccupied as required by local activity being present or not. This advanced 
occupancy functionality provides advantageous energy savings during occupied hours without sacrificing occupant comfort. All 
Terminal Equipment Controllers can be ordered with or without a factory installed PIR cover ( see ordering notes below ). 
 
The compatible VC3000 Series Line Voltage Switching Transformer Relay Pack(s) operate as slave unit(s) under the control of 
a single master VTR73XX Terminal Equipment Controller. A single VTR73XX Terminal Equipment Controller can control up to 
10 VC3000 Series Relay Pack. The VC3000 Series Relay Packs are line-powered units. They locally contain all the relay 
outputs for fan switching and valve control. Models are also available for extra monitoring / control inputs of the Fan Coil Units. 

The additional following documents are available at: 

www.viconics.com

 

 

PIR Hospitality application information and examples, are available on document: 

APP-HOSPITALITY-PIR-VTR73-Guide-Exx

 

 

HVAC Fan Coil application information and examples, are available on document: 

APP-VTR7300-PIR-Exx

 

 

Information on installation of the Transformer Relay Pack (VC3000E), is available on document 

LIT-VC3000-Exx

 

 

PIR cover installation information is available on document: 

PIR Cover Installation-Exx 

 

Information on the BACnet models (VTR73xxX5x00B), is available on document 

ITG-VTR73-PIR-BAC-Exx

 

 

Information on the Wireless models (VTR3xxX5x00W), is available on documents: I

TG-VWG-40-BAC-Exx

 and 

MAN Wireless Stat Driver 

Guide-Exx

 

 

VTR73XXA models available 

 

 

 

Viconics part number 

VTR7300A5x00(x) 

VTR7350A5x00(x) 

VTR7305A5x00(x) 

VTR7355A5x00(x) 

Primary market 

User interface definition 

Commercial and institution applications 

Hotels and lodging applications 

On board %RH sensor 

For dehumidification strategy 

None Yes None Yes 

 

Ordering Information Notes: 

The

 (X)

 at the end of the model number represents available communication options:  

 

X = none

 for Stand-alone 

 

X = B

 for BACnet MS-TP 

 

X = W

 for Wireless 

 

The Terminal Equipment Controllers can be ordered with a factory installed PIR cover. Please use (5500) extension instead of 
the (5000) only extension. The Terminal Equipment Controllers ordered without a PIR cover can be retrofitted with a separate 
PIR accessory cover afterwards if required.  

 

Ordering examples:  

  A VTR7305AW5500B is for a wall mounted Terminal Equipment Controller with a hotel / lodging interface with a factory 

mounted PIR cover and an MS-TP BACnet communication interface. 

  A VTR7350A5000W is for a wall mounted Terminal Equipment Controller with a commercial / institution interface and a 

wireless communication interface. The Terminal Equipment Controller can be retrofitted with a separate PIR accessory 
cover afterwards if required. 

 

 
028-0298_R0_LIT-VTR7300-PIR-E00.doc 

 

 

www.viconics.com / [email protected] 

 

VTR73x5X Lodging          VTR73x0X Commercial 

Содержание VTR73 Series

Страница 1: ...000 Series Line Voltage Switching Transformer Relay Pack s operate as slave unit s under the control of a single master VTR73XX Terminal Equipment Controller A single VTR73XX Terminal Equipment Contro...

Страница 2: ...el dependent The VC3xxxX Relay Pack supplies power to the wall VTR73xxA Terminal Equipment Controller The VTR73xxA Controller operates the VC3xxxX Relay Pack s via a simple communication bus A maximum...

Страница 3: ...or is opened any movements detected by the remote PIR sensor or the PIR accessory cover will be ignored Use a Normally Closed contact switching device Contact opened Door opened Contact closed Door cl...

Страница 4: ...ews in mounting holes on each side of the base Fig 4 8 Gently swing back the circuit board on the base and push on it until the tabs lock it 9 1Strip each wire 1 4 inch 10 Insert each wire according t...

Страница 5: ...single VTR73xxA Terminal Equipment Controller From the VTR73xxA Terminal Equipment Controller to the first VC3xxxX Relay Pack o Existing or new field wires o 3 minimum required 14 22 Ga Solid or Stran...

Страница 6: ...conditional to Humidity display is model and configuration dependent Model with RH sensor built in Display function can be enabled with RH display parameter Displayed range is 10 to 90 RH Outdoor air...

Страница 7: ...ertain functions is made with configuration parameter lockout Local Setpoint Adjustment when Stp Func Dual Stp Dual Occupied Setpoints Adjustment Occupied setpoint adjustments Cooling mode Heating mod...

Страница 8: ...t will be strictly for noise comfort issues Auto Speed Fan Mode operation for sequences 2 and 3 is dependent on Auto Fan parameter When Auto Fan is set to AS Default Auto Speed during occupied periods...

Страница 9: ...erminal Equipment Controller reporting to a gateway maximum of 30 Terminal Equipment Controllers per gateway be sure you set the SAME PAN ID value both at the gateway and the Terminal Equipment Contro...

Страница 10: ...tions using a Normally Open NO or Normally Closed NC remote PIR motion sensor Occupancy mode is now set as per applied PIR function and configuration Application information and examples are available...

Страница 11: ...ed Service a backlit flashing Service alarm will be displayed on the Terminal Equipment Controller LCD screen when the input is energized It can be tied in to the AC unit control card which provides a...

Страница 12: ...from 0 to 2 Will enable heat cool operation from the same output 4 0 Pipes can access all the sequences of operation from 0 to 4 Will enable heat cool operation from different output SeqOpera Sequenc...

Страница 13: ...Terminal Equipment Controller unoccupied mode and setpoints become active The factory value or 0 0 hours Setting this parameter to its default value of 0 0 hours disables the unoccupied timer This pre...

Страница 14: ...e permanent ones and saved to EEPROM Permnent permanent Any change of occupied or unoccupied setpoints through the keypad by the user are permanent and saved to EEPROM SptFunc Local setpoint settings...

Страница 15: ...hour under normal control operation It represents the maximum number of cycles that the equipment will turn ON and OFF in one hour Note that a higher C P H will represent a higher accuracy of control...

Страница 16: ...75 lb 0 34 kg PENDING Agency Approvals all models UL UL 873 US and CSA C22 2 No 24 Canada File E27734 with CCN XAPX US and XAPX7 Canada Industry Canada ICES 003 Canada PENDING Agency Approvals all mod...

Отзывы: