Flap of throttle valve (choking valve) - opens automatically when fan is running. When you stop the fan
the flap is closed by means of counterweight. The weights should be adjusted so that the flap at full fan
power is opened to about 45 °.
1 – Manometer
2 – Signalling of the safety thermoregulator
3 – Controller ST – 81
4 – Circuit breaker
5 – Safety thermoregulator
Fig.no. 13b)
Control box with regulator ST – 81 – Hefaistos P1 E
4.5
Equipment to remove excess heat
The two way safety valve DBV 1 - 02 is used for surplus heat removal in case the water temperature
in boiler exceeds 95 °C.
In case the system is equipped with a two- way safety valve DBV 1 – 02 and it comes to the boiler
overheating (the outlet water temperature is above 95 °C) then two-way safety valve will create a cold water
circuit until the temperature drops below the limit temperature. At this moment there is closed the draining
cooling system and the inlet of cold water inlet used for refilling the system.
.
Fig.no. 14
Two-way safety valve DBV 1 – 02
Technical data on the two-way safety valve DBV 1 – 02 (made by Regulus)
Opening temperature (limit):
100 °C (+0° - 5 °C)
Maximum temperature:
120 °C
Maximum pressure on the boiler side: 400 kPa (4 bar)
Maximum pressure on the water side: 600 kPa (6 bar)
Nominal flow at
p 100 kPa (1 bar):
1,9 m
3
/h
A – cold water inlet
B – outlet to the boiler
C – outlet to the waste
D – inlet from the boiler