background image

 

 

Regulation 

5.1 

Control, safety and regulation elements 

The boiler is supplied without a superior regulation and is equipped with a control panel with control, safety and regulation elements.  
The manufacturer does not recommend operation of the boiler without regulation. A version without regulation is determined for customers who 
have their own system for boiler control. 

 

 
 
 
 
 
 
 
 
 
 
 
 

 

The electric panel of the boiler is equipped with the following elements: 

– electric panel; 

– main switch with signalling; 

3 - signalling of temperature exceeding (safety thermostat and flue gases reverse flow safety device);

 

unblocking of automatics failure;

 

– switch of low / nominal stage of the boiler; 

– line fuse of 2.5 A; 

– boiler thermostat; 

– thermo-manometer; 

– electric panel bracket; 

– safety flue-gases thermostat; 

10 

– safety operational thermostat; 

11 

– bushing with diameter of 17; 

12 

– bushing with diameter of 22. 

 

Unblocking of the safety thermostats is placed in the bottom part of the bracket of the electric panel (can be unblocked after removal of 
the front part of the cladding). 

 

unblocking of the safety thermostat (for opened systems, please leave the factory settings, i.e. 97 °C, for closed systems with a pressure 
expansion tank, it may be even set up to 105 °C);

 

unblocking of the flue gas

es reverse flow safety device (it is set at 75 °C);

 

boiler thermostat (the range is 0 

– 85 °C, the recommended setting is 85 °C);

 

line fuse of 2.5 A;

 

 

The sensor of the flue gases reverse flow safety device, placed in the horizontal draught diverter, will switch-off boiler in case of insufficient flue 
gases withdrawal. Sensors of the safety and boiler thermostats (eventually, the pump thermostat) of the thermometer are placed in the well of 
the left outer section, and the back-pressure valve that is placed in the upper part of the right outer section. 

 

The boiler is equipped (on customer's request) with one of the offered gas valves:  

1. 

HONEYWELL VK 4100 Q 2003B or VK 4100 P 2004 TWO-STAGE COMBINED ELECTROMAGNETIC VALVE EQUIPPED WITH A 
HIGH-LOW COIL (fig. No. 29) 

 

enables automatic operation of the boiler in two-stage operation mode (nominal power - low power); 

 

automatic switching-over between both stages of power is provided by the outdoor thermostat Rego typ 95001; 

 

boilers equipped with this gas valve can be equipped with a programmable regulator Honeywell CM 707 or with a superior regulation. 

2. 

HONEYWELL VK 4100 A 1002 ONE-STAGE COMBINED ELECTROMAGNETIC VALVE (fig. No. 31) 

 

the boiler can be operated with only a power that can be firmly set according to the table No. 3 (the setting can be only performed by a 
service organization trained by the manufacturer); 

 

enables connection of regulation - a programmable regulator Honeywell CM 707 or a superior regulation. 

S  4565  BF  1088  or  S  4565  BF  1112  automatics,  with  a  light  failure  signalling  and  an  unblocking  button  is  placed  on  the  body  of  VK  4100Q 
2003B or VK 4100A 1002 gas valves.  

 

3. 

SIT SIGMA 843 TWO-STAGE ELECTROMAGNETIC VALVE EQUIPPED WITH A HIGH-LOW COIL (fig. No. 30) 

 

enables automatic operation of the boiler in two-stage operation mode (nominal power - low power); 

 

automatic switching-over between both stages of power is provided by the Rego outdoor thermostat of 95001 type; 

 

boilers equipped with this gas valve can be equipped with Honeywell CM 707 programmable regulator or with a superior regulation. 

 
SIT 537 automatics are placed on SIT Sigma 843 gas valve. 
 

Содержание GARD G42 ECO

Страница 1: ...GB_2018_03...

Страница 2: ...ment 24 10 Delivery and assembly 25 10 1 Delivery and accessories content 25 10 2 Mounting procedure 25 11 Commissioning instructions for contractual service organizations 27 11 1 Verification activit...

Страница 3: ...s it is equipped with a safety device for prevention of flue gas reverse motion A two sections and three sections design is suitable for reconstruction of heat sources in separate dwelling units for s...

Страница 4: ...ating power kW 8 12 17 18 26 22 30 Weight kg 75 100 122 146 Water content l 7 9 2 11 4 13 6 Chimney throat diameter mm 80 110 130 160 Boiler sizes width mm 335 420 505 590 depth x height mm 758 957 Op...

Страница 5: ...ing of the boiler is painted with high quality komaxit painting The atmospheric burner consisted of low emission oval shaped burner pipes of new type is made of anti corrosion steel with high operatio...

Страница 6: ...cladding 10 cladding rear part 11 electric panel bracket 12 electric panel 13 safety flue gases thermostat 14 safety operational thermostat 15 boiler thermostat with a turning knob 16 thermo manomete...

Страница 7: ...the safety and boiler thermostats eventually the pump thermostat of the thermometer are placed in the well of the left outer section and the back pressure valve that is placed in the upper part of the...

Страница 8: ...tion pilot burner is not combusted during the safety time Ts 55 s Ts 25 s SIT Ts 60 s then the blocking automatics will be connected If flame is extinguished during normal operation the igniting autom...

Страница 9: ...LURE SIGNALLING B 1 SAFETY THERMOSTAT BT4 BOILER THERMOSTAT BT6 OUTDOOR THERMOSTAT S2 LOW NOMINAL POWER SWITCH Y3 2 VALVE COIL M9 EXHAUSTING VENTILATOR E1 IGNITION ELECTRODE E2 IONIZATION ELECTRODE Y1...

Страница 10: ...way valve Circulation pump Valve 2 coil Circulation pump thermostat DHW heater thermostat Room thermostat ELECTRIC PANEL Conductors colors GNYE yellow green RD red BK black BN brown BU blue LEGEND Z1...

Страница 11: ...K 4100 Q 2003 B GAS VALVE E1 IGNITING ELECTRODE E2 IONIZATION ELECTRODE BT2 FLUE GASES THERMOSTAT BT1 SAFETY THERMOSTAT BT4 OPERATION THERMOSTAT S1 MAIN SWITCH H1 BOILER UNDER VOLTAGE SIGNALLING H2 FA...

Страница 12: ...AFETY THERMOSTAT BT4 BOILER THERMOSTAT BT6 OUTDOOR THERMOSTAT S2 LOW NOMINAL POWER SWITCH Y3 2 VALVE COIL M9 EXHAUSTING VENTILATOR E1 IGNITION ELECTRODE E2 IONIZATION ELECTRODE Y1 VK 4100 Q 2003 B GAS...

Страница 13: ...entilator Three way valve Circulation pump Circulation pump thermostat DHW heater thermostat Room thermostat ELECTRIC PANEL Conductors colors GNYE yellow green RD red BK black BN brown BU blue LEGEND...

Страница 14: ...AUTOMATICS Y1 VK 4100 A 1002 GAS VALVE E1 IGNITING ELECTRODE E2 IONIZATION ELECTRODE BT2 FLUE GASES THERMOSTAT BT1 SAFETY THERMOSTAT BT4 OPERATION THERMOSTAT S1 MAIN SWITCH H1 BOILER UNDER VOLTAGE SI...

Страница 15: ...IGNALLING B 1 SAFETY THERMOSTAT BT4 BOILER THERMOSTAT BT6 OUTDOOR THERMOSTAT S2 LOW NOMINAL POWER SWITCH Y3 2 VALVE COIL M9 EXHAUSTING VENTILATOR E1 IGNITION ELECTRODE E2 IONIZATION ELECTRODE Y1 SIGMA...

Страница 16: ...way valve Circulation pump Valve 2 coil Circulation pump thermostat DHW heater thermostat Room thermostat ELECTRIC PANEL Conductors colors GNYE yellow green RD red BK black BN brown BU blue LEGEND Z1...

Страница 17: ...GMA 843 GAS VALVE E1 IGNITING ELECTRODE E2 IONIZATION ELECTRODE BT2 FLUE GASES THERMOSTAT BT1 SAFETY THERMOSTAT BT4 OPERATION THERMOSTAT S1 MAIN SWITCH H1 BOILER UNDER VOLTAGE SIGNALLING H2 FAILURE SI...

Страница 18: ...boiler with an equitherm regulator the pump operation is controlled according to the regulator program Fig 14 Characteristics of Wilo Yonos Para RS 15 7 5 pump 7 Stack heaters for domestic hot water 7...

Страница 19: ...lower supply rate the heating time of domestic hot water will be longer Important warning Set the heater thermostat at the maximum temperature of 60 C remark Regulations in Czech Republic do not allo...

Страница 20: ...anometer probe well 10 support 11 side wall part of the cladding 12 rear part of the cladding 13 electric panel bracket 14 upper part of the cladding 15 front part of the cladding 16 heating water out...

Страница 21: ...o fig 19 provided the boiler is designed so that it complies with observation of the maximum height of H 1 5 m and calculations according to table No 7 The pressure loss is minimum in this design Fig...

Страница 22: ...80 1 m with sealing 1 K 45 Elbow 45 O M with sealing 2 5 K 90 Elbow 90 O M with sealing 3 O 90 Bend 90 Rs 100 O M with sealing 2 TK 80 Pipe of 1 m with an end piece 2 M 80 Internal external cuff R 60...

Страница 23: ...provision of safety Protection against electric shock SN 33 2000 5 51 ed 3 Low voltage electric installation Part 5 51 Selection and construction of electric devices General regulations SN 33 2130 ed...

Страница 24: ...s included in the reaction of fire extract from SN EN 13501 1 A1 A1 incombustible Granite sandstone concrete bricks ceramic tiles mortars fireproof plasters A2 hardly combustible Acumin izumin herakli...

Страница 25: ...ly still wrapped in protective packing If this is not possible due to the lack of space convey the boiler without the packing holding it by its base plate In no case is allowed to lift the boiler by t...

Страница 26: ...be deposited in the distributions or the heating radiators and consequently could cause a damage of the pump Water serving for watering the heating system has to be clean and colorless without suspen...

Страница 27: ...t is recommended to set temperature to 85 C heater thermostat if connected 0 90 C for a sufficiently fast hot water heating the TK boiler thermostat must be set to 85 C 3 Gas input pressure before ent...

Страница 28: ...iler 2 gas valve 1 Put the boiler into operation 2 Measure the gas input pressure 3 Before itself wait a while till operational pressure conditions on the burner are being stabled 4 If an outdoor ther...

Страница 29: ...lve is set by the manufacturer to the slowest start up see fig No 32 the MIN curve If you need to change the opening characteristics it is possible to perform setting according to the following points...

Страница 30: ...ure from the low to nominal value by means of an outdoor thermostat If the power switch is in the positions I the boiler in case of outdoor temperature higher than 0 C will be operated with the low po...

Страница 31: ...Check the burner tubes choking In case they are fouled dismount the ignition pilot burner Fig No 3 or 4 by means of a steel brush clean slightly the burner tubes perforation remove dust with help of...

Страница 32: ...bout 10 min 9 Don t put any objects made of flammable material on the boiler and within a distance smaller than the safe distance from it see chapter no 9 2 10 The user is obliged to put a professiona...

Страница 33: ...out in case of fine impurities the dimensions of which are the same as the filter mesh diameter the whole gas valve must be exchanged Boiler cannot be ignited the safety thermostat is switched off on...

Страница 34: ...operator VIADRUS a s provides an extended warranty period for the boiler drum of the boiler for 60 months from the sale date but not longer than 66 months from the dispatch date from VIADRUS a s The c...

Страница 35: ...wer and high temperature mode 4 90 93 At 30 of nominal heating power and low temperature mode P1 2 4 kW At 30 of nominal heating power and low temperature mode 1 89 21 Auxiliary electric energy consum...

Страница 36: ...d low temperature mode 1 90 69 Auxiliary electric energy consumption Other items At full load elmax 0 010 kW Heat loss in standby mode Pstby 0 099 kW At partial load elmin 0 003 kW Electric energy con...

Страница 37: ...d low temperature mode 1 90 79 Auxiliary electric energy consumption Other items At full load elmax 0 010 kW Heat loss in standby mode Pstby 0 095 kW At partial load elmin 0 003 kW Electric energy con...

Страница 38: ...and low temperature mode 1 90 76 Auxiliary electric energy consumption Other items At full load elmax 0 010 kW Heat loss in standby mode Pstby 0 114 kW At partial load elmin 0 003 kW Electric energy c...

Страница 39: ...tion of resources SN EN 13428 SN EN 13427 YES 2 Repeated use SN EN 13429 NO 3 Material recycling SN EN 13430 YES NO i 4 Energy evaluation SN EN 13431 YES NO a 5 The use by composting and biodegradatio...

Страница 40: ...ificate for the customer the user The record of performed warranty and after warranty repairs and regular annual checks of the product Record date Performed activity Contractual service organization s...

Страница 41: ......

Страница 42: ......

Страница 43: ......

Страница 44: ......

Отзывы: