Dear customer, 
We thank you that you have bought a gas VIADRUS GARDE G42 ECO boiler, thus having shown your confidence in VIADRUS brand. 
In order to accustom to correct manipulation with your new product, before installation and commissioning, please carefully acquaintance with 
the  instruction  manual  (mainly, chapter 12 

– 

Operation with the stove by an user, chapter 13  - Maintenance, and chapter No. 14 

– 

Important 

warnings). Please observe the below mentioned information, and mainly perform specified annual checks by a professional company, in order 
to ensure a long-term trouble-free operation to your and our satisfaction. 

 
 

Produced versions of boilers 

1.1 

Order 

Please specify in your order a specification code for ordering

VIADRUS GARDE G42 ECO x

1

 x

x

x

x

x

x

7

 

 

x

1

 

Size: 

2

: 2-sections design

  

3

: 3-sections design 

4

: 4-sections design 

5

: 5-sections design 

x

2

 

Fuel: 

Z:

 natural gas 

x

3

 

Flue gases 
exhaust: 

0

: without forced flue gases exhaust  

V

: forced flue gases exhaust  

x

4

 

Gas valve: 

1

: 1 

– stage gas valve 

2

: 2 

– stage gas valve 

x

5

 

Regulation: 

0

: standard delivery  

1

: CM 707 space thermostat  

(on customer's request, pump's  thermostat, outdoor thermostat, type 95001) 

x

6

 

Burner: 

T

: low-

emission burner Třinec 

x

7

 

Design: 

H

: Honeywell 

S

: SIT 

 

Tab. №. 1 

Produced versions 

Boiler's basic versions 

Size 

Fuel 

Flue gases 

exhaust 

Gas valve 

Regulation 

Burner: 

Design 

 

NG boiler  

– stage gas valve  

 

 

 

 

 

 

 

 

 

 

 

3 sect. 

 

4 sect. 

 

5 sect. 

 

NG boiler  

– stage gas valve 

2 sect. 

 

 

3 sect. 

 

 

4 sect. 

 

 

5 sect. 

 

 

 
 

Boiler usage and advantages 

 
The  cast-iron  sectional  gas  boiler  VIADRUS  GARDE  G42  ECO  (hereunder  referred  as  in  general  G42  ECO)  equipped  with  an  atmospheric 
burner  is  destined  for  combustion  of  low-pressure  natural  gas.  The  boiler  is  being  produced  in  design 

B

11BS

,  it  means  it  is  equipped  with  a 

safety device for prevention of flue-gas reverse-motion. A two-sections and three-sections design is suitable for reconstruction of heat sources 
in separate dwelling units, for small accommodation and recreation facilities. Bigger sizes comply with requirements for heating of single-family 
houses, shops, schools, etc.  

The boiler is manufactured as a warm-water boiler with forced circulation and work overpressure up to 400 kPa (4 bar). Before dispatching, it is 
tested for tightness with testing overpressure of 800 kPa (8 bar); it complies with tests of insulating and transition resistance. 

In  case  of  requirement  for  preferential  heating  of  domestic  hot  water,  you  may  separately  order  VIADRUS  OV  100  L  stationary  heater,  the 
design of which complies with the G42 ECO boiler. 

The electric connection of the boiler is adapted for connection of a stack heater of domestic hot water with provision of its preferential heating.  

Thanks to the top-quality structure of its cast-iron sections, the low-temperature cast-iron boiler prevents creation of condensate and, by this, a 
danger of low-temperature corrosion. 

The  heat-delivery  (convective)  surfaces  of  the  boiler  drum  reach  high  usage  of  heat  that  is  contained  in  flue  gases.  Due  to  the  use  of  high-
quality cast iron, the boiler is able to transfer fully the received heat to heating water uniformly in all parts of the boiler. 

There is no necessity to maintain heating water at temperature above 50 °C because no damage due to low-temperature corrosion arise in this 
boiler at temperatures of return water about 30 °C. 

While designing the boiler, we use in full range empiric knowledge of boilers operation within our climatic conditions, whereas, especially in the 
transition time of the heating period, boilers are often operated with low temperature of heating water. On one hand, such operating increases 
boiler  efficiency,  but  on  the  other  hand,  it  however  increases  a  risk  of  low-temperature  corrosion  of  the  heat-exchanger.  But  even  such 
economic operation does not cause this negative phenomenon. 
  

Содержание GARD G42 ECO

Страница 1: ...GB_2018_03...

Страница 2: ...ment 24 10 Delivery and assembly 25 10 1 Delivery and accessories content 25 10 2 Mounting procedure 25 11 Commissioning instructions for contractual service organizations 27 11 1 Verification activit...

Страница 3: ...s it is equipped with a safety device for prevention of flue gas reverse motion A two sections and three sections design is suitable for reconstruction of heat sources in separate dwelling units for s...

Страница 4: ...ating power kW 8 12 17 18 26 22 30 Weight kg 75 100 122 146 Water content l 7 9 2 11 4 13 6 Chimney throat diameter mm 80 110 130 160 Boiler sizes width mm 335 420 505 590 depth x height mm 758 957 Op...

Страница 5: ...ing of the boiler is painted with high quality komaxit painting The atmospheric burner consisted of low emission oval shaped burner pipes of new type is made of anti corrosion steel with high operatio...

Страница 6: ...cladding 10 cladding rear part 11 electric panel bracket 12 electric panel 13 safety flue gases thermostat 14 safety operational thermostat 15 boiler thermostat with a turning knob 16 thermo manomete...

Страница 7: ...the safety and boiler thermostats eventually the pump thermostat of the thermometer are placed in the well of the left outer section and the back pressure valve that is placed in the upper part of the...

Страница 8: ...tion pilot burner is not combusted during the safety time Ts 55 s Ts 25 s SIT Ts 60 s then the blocking automatics will be connected If flame is extinguished during normal operation the igniting autom...

Страница 9: ...LURE SIGNALLING B 1 SAFETY THERMOSTAT BT4 BOILER THERMOSTAT BT6 OUTDOOR THERMOSTAT S2 LOW NOMINAL POWER SWITCH Y3 2 VALVE COIL M9 EXHAUSTING VENTILATOR E1 IGNITION ELECTRODE E2 IONIZATION ELECTRODE Y1...

Страница 10: ...way valve Circulation pump Valve 2 coil Circulation pump thermostat DHW heater thermostat Room thermostat ELECTRIC PANEL Conductors colors GNYE yellow green RD red BK black BN brown BU blue LEGEND Z1...

Страница 11: ...K 4100 Q 2003 B GAS VALVE E1 IGNITING ELECTRODE E2 IONIZATION ELECTRODE BT2 FLUE GASES THERMOSTAT BT1 SAFETY THERMOSTAT BT4 OPERATION THERMOSTAT S1 MAIN SWITCH H1 BOILER UNDER VOLTAGE SIGNALLING H2 FA...

Страница 12: ...AFETY THERMOSTAT BT4 BOILER THERMOSTAT BT6 OUTDOOR THERMOSTAT S2 LOW NOMINAL POWER SWITCH Y3 2 VALVE COIL M9 EXHAUSTING VENTILATOR E1 IGNITION ELECTRODE E2 IONIZATION ELECTRODE Y1 VK 4100 Q 2003 B GAS...

Страница 13: ...entilator Three way valve Circulation pump Circulation pump thermostat DHW heater thermostat Room thermostat ELECTRIC PANEL Conductors colors GNYE yellow green RD red BK black BN brown BU blue LEGEND...

Страница 14: ...AUTOMATICS Y1 VK 4100 A 1002 GAS VALVE E1 IGNITING ELECTRODE E2 IONIZATION ELECTRODE BT2 FLUE GASES THERMOSTAT BT1 SAFETY THERMOSTAT BT4 OPERATION THERMOSTAT S1 MAIN SWITCH H1 BOILER UNDER VOLTAGE SI...

Страница 15: ...IGNALLING B 1 SAFETY THERMOSTAT BT4 BOILER THERMOSTAT BT6 OUTDOOR THERMOSTAT S2 LOW NOMINAL POWER SWITCH Y3 2 VALVE COIL M9 EXHAUSTING VENTILATOR E1 IGNITION ELECTRODE E2 IONIZATION ELECTRODE Y1 SIGMA...

Страница 16: ...way valve Circulation pump Valve 2 coil Circulation pump thermostat DHW heater thermostat Room thermostat ELECTRIC PANEL Conductors colors GNYE yellow green RD red BK black BN brown BU blue LEGEND Z1...

Страница 17: ...GMA 843 GAS VALVE E1 IGNITING ELECTRODE E2 IONIZATION ELECTRODE BT2 FLUE GASES THERMOSTAT BT1 SAFETY THERMOSTAT BT4 OPERATION THERMOSTAT S1 MAIN SWITCH H1 BOILER UNDER VOLTAGE SIGNALLING H2 FAILURE SI...

Страница 18: ...boiler with an equitherm regulator the pump operation is controlled according to the regulator program Fig 14 Characteristics of Wilo Yonos Para RS 15 7 5 pump 7 Stack heaters for domestic hot water 7...

Страница 19: ...lower supply rate the heating time of domestic hot water will be longer Important warning Set the heater thermostat at the maximum temperature of 60 C remark Regulations in Czech Republic do not allo...

Страница 20: ...anometer probe well 10 support 11 side wall part of the cladding 12 rear part of the cladding 13 electric panel bracket 14 upper part of the cladding 15 front part of the cladding 16 heating water out...

Страница 21: ...o fig 19 provided the boiler is designed so that it complies with observation of the maximum height of H 1 5 m and calculations according to table No 7 The pressure loss is minimum in this design Fig...

Страница 22: ...80 1 m with sealing 1 K 45 Elbow 45 O M with sealing 2 5 K 90 Elbow 90 O M with sealing 3 O 90 Bend 90 Rs 100 O M with sealing 2 TK 80 Pipe of 1 m with an end piece 2 M 80 Internal external cuff R 60...

Страница 23: ...provision of safety Protection against electric shock SN 33 2000 5 51 ed 3 Low voltage electric installation Part 5 51 Selection and construction of electric devices General regulations SN 33 2130 ed...

Страница 24: ...s included in the reaction of fire extract from SN EN 13501 1 A1 A1 incombustible Granite sandstone concrete bricks ceramic tiles mortars fireproof plasters A2 hardly combustible Acumin izumin herakli...

Страница 25: ...ly still wrapped in protective packing If this is not possible due to the lack of space convey the boiler without the packing holding it by its base plate In no case is allowed to lift the boiler by t...

Страница 26: ...be deposited in the distributions or the heating radiators and consequently could cause a damage of the pump Water serving for watering the heating system has to be clean and colorless without suspen...

Страница 27: ...t is recommended to set temperature to 85 C heater thermostat if connected 0 90 C for a sufficiently fast hot water heating the TK boiler thermostat must be set to 85 C 3 Gas input pressure before ent...

Страница 28: ...iler 2 gas valve 1 Put the boiler into operation 2 Measure the gas input pressure 3 Before itself wait a while till operational pressure conditions on the burner are being stabled 4 If an outdoor ther...

Страница 29: ...lve is set by the manufacturer to the slowest start up see fig No 32 the MIN curve If you need to change the opening characteristics it is possible to perform setting according to the following points...

Страница 30: ...ure from the low to nominal value by means of an outdoor thermostat If the power switch is in the positions I the boiler in case of outdoor temperature higher than 0 C will be operated with the low po...

Страница 31: ...Check the burner tubes choking In case they are fouled dismount the ignition pilot burner Fig No 3 or 4 by means of a steel brush clean slightly the burner tubes perforation remove dust with help of...

Страница 32: ...bout 10 min 9 Don t put any objects made of flammable material on the boiler and within a distance smaller than the safe distance from it see chapter no 9 2 10 The user is obliged to put a professiona...

Страница 33: ...out in case of fine impurities the dimensions of which are the same as the filter mesh diameter the whole gas valve must be exchanged Boiler cannot be ignited the safety thermostat is switched off on...

Страница 34: ...operator VIADRUS a s provides an extended warranty period for the boiler drum of the boiler for 60 months from the sale date but not longer than 66 months from the dispatch date from VIADRUS a s The c...

Страница 35: ...wer and high temperature mode 4 90 93 At 30 of nominal heating power and low temperature mode P1 2 4 kW At 30 of nominal heating power and low temperature mode 1 89 21 Auxiliary electric energy consum...

Страница 36: ...d low temperature mode 1 90 69 Auxiliary electric energy consumption Other items At full load elmax 0 010 kW Heat loss in standby mode Pstby 0 099 kW At partial load elmin 0 003 kW Electric energy con...

Страница 37: ...d low temperature mode 1 90 79 Auxiliary electric energy consumption Other items At full load elmax 0 010 kW Heat loss in standby mode Pstby 0 095 kW At partial load elmin 0 003 kW Electric energy con...

Страница 38: ...and low temperature mode 1 90 76 Auxiliary electric energy consumption Other items At full load elmax 0 010 kW Heat loss in standby mode Pstby 0 114 kW At partial load elmin 0 003 kW Electric energy c...

Страница 39: ...tion of resources SN EN 13428 SN EN 13427 YES 2 Repeated use SN EN 13429 NO 3 Material recycling SN EN 13430 YES NO i 4 Energy evaluation SN EN 13431 YES NO a 5 The use by composting and biodegradatio...

Страница 40: ...ificate for the customer the user The record of performed warranty and after warranty repairs and regular annual checks of the product Record date Performed activity Contractual service organization s...

Страница 41: ......

Страница 42: ......

Страница 43: ......

Страница 44: ......

Отзывы: