Battery charger / inverter COMBI-GAMMA
66
090138.02
Use these settings to switch off the Aux-Relay 1 when battery voltage becomes higher
•
than a certain limit (E2-05) for a certain time (E2-06)
Note: If E2-06=0 sec (Initial setting), then E2-05 is ignored.
*
E2-07: Charging for ? sec
This setting switches the Aux-Relay 1 OFF when the
•
AC CHARGER started for a certain time
(E2-07). This can be useful when the Aux-Relay 1 is for instance used a low battery alarm.
Use the
•
Set Udc Lower than ? Voltage (E1-03) setting to start the alarm and use this set-
ting (E2-07) to stop it.
Note: As along as the battery voltage is lower than the specified limit (E1-03), the alarm
*
will be active.
E2-08: Fan OFF for ? sec
This will switch the Aux-Relay 1 OFF when the internal fan switches off. This can be used
•
together with the E1-08: Fan ON for ? sec setting to drive an external fan.
E2-09: Charge finished for ? Min (When E2-09=0, ignore this setting)
This condition becomes active when the charge bulk phase is finished for a certain time
•
(E2-09).
For the charge curve, take a look at for instance the
•
Charge Current (D1-08) setting.
This is useful when the Aux-Relay 1 is used to start a generator. Once started, one might
•
want to keep the generator on until the batteries are more or less charged.
E2-10: Aux-Relay 1 not ON for ? minutes (When E2-10=0, ignore this setting)
If one does not need special off condition, one can use this setting and the Aux-Relay
•
1 will switch off automatically when there has been no ON condition for a certain time
(E2-10).
E2-11: AC IN loss for ? sec (When E2-11=0, ignore this setting)
This setting will switch off Aux-Relay1 if the RMS value of
•
AC IN voltage is too low for a
certain time (E2-11).
This AC level is determined by the
•
AC IN Low Disconnect (B2-01) setting.
Use this setting (E2-11) to disable re-starting of a generator which is switched off by
•
hand when the Aux-Relay 1 is used to generate a start signal for that generator.
E2-12: No Temp. Alarm Select (When E2-13=0, ignore this setting)
E2-13: No Temp. Alarm for ? sec
If you want to switch off the Aux-Relay 1 when there is no over temperature alarm, this
•
setting (E2-12) can be used to choose between pre-alarm or normal alarm.
As with other Aux-Relay 1 setting, a delay value must be specified also. This can be
•
done with the Delay value for set Aux-Relay 1 OFF when No Overtemperature Alarm