Battery charger / inverter COMBI-GAMMA
46
090138.02
Menu
Group
Function
Constant
LCD Display
Range
Unit
Factory Setting
Remark
P
age
E1-15
Overload Alarm Sel
0~1
1
0
0:Alarm 1:Pre-
alarm
65
E1-16
OL Alarm for ? sec
0~255
1sec
0sec
65
E1-17
Udc Ripple Alarm Sel
0~1
1
0
0:Alarm 1:Pre-
alarm
65
E1-18
UdcRipAlarm for ? sec
0~255
1sec
0sec
65
Programming
E
Aux
-Relay
E2
Set Aux
-
Relay 1
OFF
E2-01
Load Lower than ? A
NOTE 3
0.01A
NOTE 3
E2-02
Load Lower for ? sec
0~255
1sec
0sec
65
E2-03
Udc Lower than ? V
NOTE 3
1V
NOTE 3
65
E2-04
Udc Lower for ? sec
0~255
1sec
0sec
65
E2-05
Udc Higher than ? V
NOTE 3
1V
NOTE 3
65
E2-06
Udc Higher for ? sec
0~255
1sec
0sec
65
E2-07
Charging for ? sec
0~255
1sec
0sec
66
E2-08
Fan Off for ? sec
0~255
1sec
0sec
66
E2-09
Charge Finished ? Min
0~1000
1min
0
66
E2-10
RY1 not ON for ? mins
0~1000
1min
0
66
E2-11
AC IN Loss for ? sec
0~255
1sec
0sec
66
E2-12
No T
emp. Alarm Sel
0~1
1
0
0:Alarm 1:Pre-
alarm
66
E2-13
No T
emp. Alarm ? sec
0~255
1sec
0sec
66
E2-14
No Low Bat. Alarm Sel
0~1
1
0
0:Alarm 1:Pre-
alarm
67
E2-15
No Low Bat for ? sec
0~255
1sec
0sec
67
E2-16
No OL Alarm Sel
0~1
1
0
0:Alarm 1:Pre-
alarm
67
E2-17
No OL Alarm for ? sec
0~255
1sec
0sec
67
E2-18
No UdcRipple Alarm
Sel
0~1
1
0
0:Alarm 1:Pre-
alarm
67
E2-19
No UdcRipple Alarm
?sec
0~255
1sec
0sec
67